8
Parts and Accessories
Instrument Power Fuse
Chromalox Part Number
Description
0024-01097
Littlefuse # 225 002 2 AG 2AMP
I
2
T Fuses for 500 Vac Applications
0024-07634
200 Amp I
2
t Fuse
0024-07630
250 Amp I
2
t Fuse
0024-07632
400 Amp I
2
t Fuse
0024-03116
500 Amp I
2
t Fuse
0024-07633
700 Amp I
2
t Fuse
0024-03118
800 Amp I
2
t Fuse
0024-03200
1000 Amp I
2
t Fuse
I
2
T Fuses for 575 Vac Applications
0024-07644
125 Amp I
2
t Fuse
0024-07645
175 Amp I
2
t Fuse
0024-07636
250 Amp I
2
t Fuse
0024-07637
400 Amp I
2
t Fuse
0024-07638
500 Amp I
2
t Fuse
0024-07639
700 Amp I
2
t Fuse
0024-07640
800 Amp I
2
t Fuse
0024-07646
1000 Amp I
2
t Fuse
0024-01191
1200 Amp I
2
t Fuse
Fans
Chromalox Part Number
Description
0045-00231
120 Vac rated Fan
0045-00235
230 Vac rated Fan
Crimp Lug Chart
For Open Design 400 - 1200 Amp and all Touch-Safe Models:
Conductor Size
Chromalox Part #
Panduit Part #
#8 AWG (10mm
2
)
0135 - 10002
LCD8 - 14A - L
#6 AWG or #6 Weld (16mm
2
)
0135 - 10003
LCD6 - 14A - L
#4 AWG or #4 Weld (25mm
2
)
0135 - 10004
LCD4 - 14A - L
#2 AWG (35mm
2
)
0135 - 10005
LCD2 - 56B - Q
#1 AWG or #2 Weld (50mm
2
)
0135 - 10006
LCD1 - 56C - E
#1/0 AWG or #1 Weld (70mm
2
)
0135 - 10007
LCD1/0 - 12 - X
#2/0 AWG or #1/0 Weld (70mm
2
)
0135 - 10008
LCD2/0 - 12 - X
#3/0 AWG or #2/0 Weld (95mm
2
)
0135 - 10009
LCD3/0 - 12 - X
#4/0 AWG or #3/0 Weld (120mm
2
)
0135 - 10010
LCD4/0 - 12 - X
250 MCM or #4/0 Weld (150mm
2
)
0135 - 10011
LCD250 - 12 - X
300 MCM (150mm
2
)
0135 - 10012
LCD300 - 12 - X
350 MCM (185mm
2
)
0135 - 10013
LCD350 - 12 - 6
400 MCM (240mm
2
)
0135 - 10014
LCD400 - 12 - 6
500 MCM (240mm
2
)
0135 - 10015
LCD500 - 12 - 6
SCR Replacement
Be sure to replace thermstrate interface material and torque as follows:
MFG Part #
SCR Part #
Thermstrate Part #
Torque inch/lb
Torque inch/lb
to Heat Sink to Terminals
SKKT92
0002 - 47560
0029 - 00700
44 inch/lb (5 Nm)
26 inch/lb (3Nm)
SKKT162
0002 - 47559
0029 - 00822
44 inch/lb (5 Nm)
44 inch/lb (5 Nm)
SKKT250
0002 - 47537
0029 - 00719
44 inch/lb (5 Nm)
80 inch/lb (9 Nm)
SKKT500
0002 - 47557
0029 - 00814
44 inch/lb (5 Nm)
106 inch/lb (12 Nm)
MaxPac I, II, and III
Accessories:
Part Number Description
0135 - 28096 Plug-In Shorted SCR Detection Board
0135 - 28095 Plug-In Proportional DOT-Fired Control Board
0135 - 28093 SCR Trigger Board
0135 - 28094 On/Off Main Firing Board
0135 - 20117 Potentiometer & Remote/Manual Switch
For CE Application, the Following Filters are Required:
0005 - 60055 Line Filter Single Phase 230 Vac
0005 - 60057 Line Filter 120 - 230 Vac 3 Amps
0005 - 60056 Line Filter Three Phase 440 Vac
MaxPac IP
Accessories:
Part Number Description
0135 - 28002 Firing Circuit 120, 240 Vac
0135 - 28006 Firing Circuit 208, 277, 480 Vac
0135 - 28037 Firing Circuit 380 Vac