Chromalox MaxPac I Скачать руководство пользователя страница 24

- 23 -

© 2014 Chromalox

®

, Inc.

1-888-996-9258

1. Set Current Limit (I LIM) pot to 0% for full current output (CCW). 

Current Limit is for limiting current for loads that have 
extreme hot to cold resistance ratios or are overrated. We 
recommend for these types of loads to adjust I LIM (Cur

-

rent Limit) to 50% or less. This will also decrease voltage 
as well as current. 0% Current Limit gives 100% current 
output (CCW). 100% Current Limit gives 10% current 
output (CW).

2. Set Manual (MAN) pot to zero so unit will not be biased above  
  input (CCW).

Manual control adjustment provides a means of setting 

the output level of the MaxPac Power Pak in the absence 
of controlling instrumentation. The manual control signal 

value “adds” to the controlling instrument to set mini

-

mum output. The desired output power level may be set 

by adjusting the manual control. This value of output will 

then be present even in the absence of a control signal.

3. Set Remote Manual pot to zero output so unit will not be biased  
  above input (CCW). (Jumper pins 4 & 5 if not used.) 

Remote Manual control adjustment provides a means 

of setting the output level of the MaxPac Power Pak in 
the absence of controlling instrumentation. The Remote 
Manual control is also effective when a control signal 
is connected. The Remote Manual control signal value 

“adds” to the controlling instrument to set minimum 

output. The desired output power level may be set by 

adjusting the Remote Manual control. This value of out

-

put will then be present even in the absence of a control 

signal. Connect Remote Manual pot wire to Pin 4 (CCW), 
Pin 5 (W), and Pin 6 (CW) of plug-in connector.

4. Check for open contact for Emergency Shutdown.

Emergency Shutdown inhibits all SCR trigger pulses 

regardless of the level of the input signal or manual 

potentiometer. For Emergency Shutdown, close contact 
Pin 7 to Pin 8 of plug-in connector. Leave contacts open 

for operation.

5. Check for polarity of input signal.

6. Adjust input signal to low end of scale.

Zero Adjust control sets the power output starting point 

or reference. Thus, it effectively cancels positive inputs   
to the MaxPac Power Pak.

    EXAMPLE:   0 - 5 mA input à set to 0 mA input
 

4 - 20 mA input à set to 4 mA input

 

 

7. With power off, connect line voltage and load as shown.

8. Connect meter to input and output.

 WARNING: Set meter to correct scale to read proper input  

 

or output.

9. Apply power to unit.

10. Adjust input signal to low end of scale.

11. Using the Zero pot, adjust the output voltage just to zero volts.

12. Adjust input signal to top end of scale.

Gain Adjust Control sets the maximum power output for 

maximum input signal.

  EXAMPLE:  0 - 5 mA input: set to 5 mA input
   

4 - 20 mA input: set to 20 mA input

13. Using the Gain pot, adjust output voltage just to maximum  

 volts.

14. Repeat steps 11, 12, 13, and 14 until no adjustment is    
 

necessary of Zero and Gain pots for proper output voltage 

 

indication. Voltage output should increase proportionally to the  

 

signal input applied.

15. Adjust input signal to low end of scale (zero voltage output).

16. With Manual pot at zero for zero voltage output, adjust (CW) 
   to 100% for full voltage output. Voltage output should    
  increase proportionally. Return to CCW position and output will  
  decrease to zero output.

17. With Remote Manual at zero for zero voltage output, adjust  
 

(CW) to 100% for full voltage output. Voltage output should  

 

increase proportionally. Return to CCW position and output will  

 

decrease to zero output.

18. With Manual pot (CW) at 100% and I LIM (Current Limit) at 
0%,  

 

adjust I LIM towards 100% noting that voltage 

output de  

 

creases with the adjustment of the 

Current Limit pot. Adjust  

 

Current Limit pot for your 

application, if needed.

19. Turn POWER OFF and remove meters. TEST COMPLETE.

 

 

4.2.6 - Calibration (MaxPac IP):

Many high-temperature heating elements exhibit extreme hot to cold resistance ratios. Heating elements composed of Platinum, 

Molybdenum, Tungsten, and Tantalum, to name a few, draw excessive current on start-up. Depending on the mass of the elements, 
these “high starting currents” may exist for extended periods of time. Generally, once the elements have achieved their normal operat

-

ing temperatures, the current drawn through the MaxPac Power Pak will fall within the rating of the unit. For these types of loads, we 

recommend adjusting the I LIM (Current Limit) to 50% or less. This will decrease voltage as well as current.

Содержание MaxPac I

Страница 1: ...PK480 2 P N 0037 75428 User s Manual www chromalox com 800 443 2640 2014 Chromalox Inc...

Страница 2: ...age Protection MOV Protection Built In Power Distribution Features for the MaxPac I II and III include Zero Crossover Firing Isolated Control Circuit On Off Control Inputs 120 thru 240 Vac 5 32 Vdc Dr...

Страница 3: ...g 8 4 2 Wiring 11 4 2 1 Touch Safe Design 11 4 2 2 Cover Removal and Installation 12 4 2 3 Power Load Wiring 12 4 2 4 Instrument Power 16 4 2 5 Grounding 16 4 2 6 Command Signal Wiring 17 4 2 7 Calibr...

Страница 4: ...reduce the risk of personal injury to persons from fire and electrical shock hazards Safety Alert Symbol International Shock Electrocution Symbol Each safety message is preceded by a safety alert symb...

Страница 5: ...d thermal shock The power SCR assemblies consist of one two or three pairs of SCRs connected back to back with an optional semiconductor fuse RC Snubber and MOV protection The firing circuit is based...

Страница 6: ...ich to mount your MaxPac please consider the following Temperature When mounting the SCR unit in a control panel attention should be paid to the enclosure tempera ture The SCR is rated to perform at i...

Страница 7: ...er of two directions The output power can only be connected from one direction The three mounting configurations are shown below MaxPac II Three Phase Two Leg Shown Open designs above 300 amps and all...

Страница 8: ...es of Proper Air Flow Pagoda Top Fan Air Louvers Louvers MaxPac Air Fan MaxPac Fan Enclosure Air Enclosure Fan Filter Forced Air In Forced Air Out Louvers Since hot air rises naturally it is not recom...

Страница 9: ...ctory 4 Installation Please read all information in this section before beginning the installation of your MaxPac Installation of the MaxPac requires three steps 1 Mounting 2 Power wiring 3 120 or 230...

Страница 10: ...mm 6 0 153mm 7 28 185mm FIRING PACKAGE FAN END 0 280 7 11mm 6 HOLES 7 2 183mm 0 0 0mm 1 3 33mm 7 3 185mm 13 3 337mm 14 6 371mm 12 0 305mm 13 3 338mm FIRING PACKAGE FAN END 0 280 7 11mm 6 HOLES 5 12 13...

Страница 11: ...8 11 7 298mm 0 0 0mm 1 3 33mm 9 3 237mm 13 31 338mm 14 62 371mm 21 4 543mm 22 4 568mm FIRING PACKAGE FAN END 3125 7 94mm 8 HOLES 5 3 135mm 5 8 148mm 0 0 0mm 1 3 33mm 11 3 28mm 16 3 414mm 17 6 448mm 9...

Страница 12: ...t installation wiring that is in accordance with the National Electrical Code and any local standards that may be applicable WARNING Hazardous Voltage Only qualified personnel should perform electrica...

Страница 13: ...Lift the cover from the base Install Wiring 3 Attach the wires to the bus bars in accordance with the instructions in the next section 4 Choose the entrance and exit directions for the wiring as desi...

Страница 14: ...L2 X1 X3 L2 Connection is NOT on MaxPac Four Wire 3 Leg Control MAX PAC III L1 L2 L3 X1 X2 X3 N N Connection is NOT on MaxPac IMPORTANT The I2 t fuses installed on the SCR are designed to protect the...

Страница 15: ...the SCR are designed to protect the SCR from faults on the load connection side They are NOT intended to provide wire protection CAUTION Three Wire 3 Leg Control MAX PAC III L1 L2 L3 X1 X2 X3 Single P...

Страница 16: ...side of the bus bar as shown to maintain required electrical clearances Illustration 2 View From Top Touch Safe Units 100 400 Amps Input Bus Up to 3 1 0 300 mcm 70 mm2 150 mm2 Up to 2 350 500 mcm 185...

Страница 17: ...the wire in the holes that maximize the distance for the wire to exit the enclosure This maximizes the distance from the cover to the non insulated connector When using the power distribution feature...

Страница 18: ...g 7 on page 21 1 5 Vdc Terminal J2 5 7 see Fig 5 on page 21 0 10 Vdc Terminal J2 10 7 see Fig 8 on page 21 4 20 mA Terminal J2 6 7 see Fig 6 on page 21 Auto Manual Input The MaxPac I II and III can be...

Страница 19: ...nal level compatible with the optional proportional firing board The plug in receptacle for the optional proportional board allows for an easy upgrade to proportional control The drive signal to the S...

Страница 20: ...stem An external indicating lamp or relay can be connected to J1 5 6 see Fig 2 on page 21 This indicator must be rated for the instrument power applied to J1 1 2 Three diagnostic LEDs show which SCR p...

Страница 21: ...rd 0135 28096 When this jumper is installed latching operation is achieved The drawing below shows the Shorted SCR Detection board Heat Sink Over Temperature An external lamp or relay may be connected...

Страница 22: ...L INPUT SIG 1 5 VDC PROPORTIONAL INPUT 4 5 2 3 1 J2 10 COMMON 7 8 9 6 5 J1 10 7 8 9 6 5 1 K J2 2 4 3 1 J2 2 4 3 1 J1 J3 120 230 INSTRUMENT POWER REQUIRED ON ALL CONFIGURATIONS 120 230 INSTRUMENT POWER...

Страница 23: ...are correctly applied Also make sure the Emergency Shutdown if used has N O contacts and jumper pins 4 5 on the 10 pin connector if remote manual bias are not used Please read the information on cali...

Страница 24: ...positive inputs to the MaxPac Power Pak EXAMPLE 0 5 mA input set to 0 mA input 4 20 mA input set to 4 mA input 7 With power off connect line voltage and load as shown 8 Connect meter to input and outp...

Страница 25: ...Voltage Output Indicator Output 100 mA Instrument Power Shorted SCR AC Voltage Output Indicator Output 100 mA Instrument Power MaxPac I II and III MaxPac IP Control Inputs Accepts all of the followin...

Страница 26: ...suffer corrosion Periodically check the power module for corrosion Damage Periodically check for rodent damage to wiring and other components Filters Many high powered control enclosures rely on blow...

Страница 27: ...oad If Demand Light is Off 1 Check incoming line power 2 Check the instrument power 3 Check the fuse on the main board 4 Verify the input signal 5 Check that remote shutdown J3 3 to 4 is open 6 Check...

Страница 28: ...ld 70mm2 0135 10008 LCD2 0 12 X 3 0 AWG or 2 0 Weld 95mm2 0135 10009 LCD3 0 12 X 4 0 AWG or 3 0 Weld 120mm2 0135 10010 LCD4 0 12 X 250 MCM or 4 0 Weld 150mm2 0135 10011 LCD250 12 X 300 MCM 150mm2 0135...

Страница 29: ...ained in accordance with Chromalox instructions Users are responsi ble for the suitability of the products to their application There is no warranty against damage resulting from corrosion misapplicat...

Страница 30: ...en Design 04 150 Amp Touch Safe Design 05 200 Amp Open Design 06 200 Amp Touch Safe Design 07 300 Amp Open Design 08 300 Amp Touch Safe Design 09 400 Amp Open Design 10 400 Amp Touch Safe Design 11 55...

Страница 31: ...tentiometer MXPC I 2 03 1 1 L1 F01 1 Typical Model Number Crimp Lug Chart Chromalox Panduit Conductor Size Torque In Lb Nm 0135 10002 LCD8 14A L 8 AWG 180 20 0135 10003 LCD6 14A L 6 AWG or 6 Weld 180...

Страница 32: ...mp Touch Safe Design 07 300 Amp Open Design 08 300 Amp Touch Safe Design 09 400 Amp Open Design 10 400 Amp Touch Safe Design 11 550 Amp Open Design 12 550 Amp Touch Safe Design 13 650 Amp Open Design...

Страница 33: ...otentiomete MXPC IP 2 03 1 1 L1 F01 1 Typical Model Number Crimp Lug Chart Chromalox Panduit Conductor Size Torque In Lb Nm 0135 10002 LCD8 14A L 8 AWG 180 20 0135 10003 LCD6 14A L 6 AWG or 6 Weld 180...

Страница 34: ...en Design 04 150 Amp Touch Safe Design 05 200 Amp Open Design 06 200 Amp Touch Safe Design 07 300 Amp Open Design 08 300 Amp Touch Safe Design 09 400 Amp Open Design 10 400 Amp Touch Safe Design 11 55...

Страница 35: ...equires Proportional Band MXPC II 2 03 1 1 L1 F01 1 Typical Model Number Crimp Lug Chart Chromalox Panduit Conductor Size Torque In Lb Nm 0135 10002 LCD8 14A L 8 AWG 180 20 0135 10003 LCD6 14A L 6 AWG...

Страница 36: ...uch Safe Design 05 200 Amp Open Design 06 200 Amp Touch Safe Design 07 300 Amp Open Design 08 300 Amp Touch Safe Design 09 400 Amp Open Design 10 400 Amp Touch Safe Design 11 550 Amp Open Design 12 55...

Страница 37: ...s Proportional Band MXPC III 2 04 1 1 L1 F02 1 Typical Model Number Crimp Lug Chart Chromalox Panduit Conductor Size Torque In Lb Nm 0135 10002 LCD8 14A L 8 AWG 180 20 0135 10003 LCD6 14A L 6 AWG or 6...

Страница 38: ...1000 6 4 2001 EN 55011 2007 Part 4 3 Contactors and 2 Conducted Disturbance Emissions Voltage motor starters EN 61000 6 4 2001 EN 55011 2007 AC semiconductor controllers and contactors for non motor l...

Страница 39: ...he Technical documentation required by Annex IV 3 of the Low Voltage Directive is maintained by Name of company and location in the European Union Year in which CE Marking was affixed 2002 Authorized...

Отзывы: