Introduction
For nearly a century, customers have relied upon Chro-
malox for premiere quality and innovative solutions for
industrial heating applications. Chromalox manufac-
tures the world’s largest and broadest line of electric
heat and control products.
The
intelliTRACE
TM
family of heat tracing products
continues to expand with its latest single or two circuit
controllers the ITC1 & ITC2. These are a complete tem-
perature control and system management solutions for
electrical heat trace applications. They are designed
for industrial applications in ordinary or Class I, Division
2. Groups A,B,C & D hazardous locations.
The
intelliTRACE
TM
ITC1 & ITC2 provides the user with
an easy to navigate menu system, continuous critical
parameter monitoring, application flexibility and equip-
ment safety precautions.
The ITC is an ideal solution either Freeze Protection or
Process Temperature control. Whether you have Ambi-
ent or Line Sensing or a combination of both, the ITC is
the affordable and complete system for you.
intelliTRACE
TM
ITC Features:
• 1 & 2 Circuit Models
• 100 – 277 VAC, 50/60 Hz
• SSR Control, 40 Amps per Circuit
• PID, On/Off or Manual Control Modes
• Selectable Soft Start Feature
• ModBus Communications
• RTU/RS485 (& 422)
• TCP/Ethernet
• Full Monitoring & Alarms
• High / Low Temperature
• High & Low Current
• GFEP & Sensor Failure
• Programmable Duty Cycle On Sensor Failure
• Alarm Indication & Announcement
• Password Protected Security Levels
• NEMA 4X Fiberglass or 316 SS Wall Mount Enclosure
• LED Indication for Power, Load & Alarm per Circuit
• Front Panel Capacitive Touch Switches
• One or two Sensor Inputs / Circuit – Min, Max & Av-
eraging
• 2 Circuit Ambient control from a single RTD sensor
• High Resolution TFT Display:
• 2 Circuits displayed / screen (on 2 Circuit unit)
• Displayed Parameters: Process Variable, Set
Point Temperature, Control Mode, Soft Start sta-
tus, Load demand, Alarm Status
Agency Approvals:
• UL, cUL Ordinary Areas, Class I Division 2 areas
• CE
Options:
• Ethernet Communications (TCP/Ethernet or web
server/Ethernet)
• Wireless Communications (Consult Sales)
• 12” x 10” x 8” NEMA 4X 316SS Wall Mount Enclosure
IMPORTANT: To comply with NEC code,
one of the following must apply.
1. Customer supplied 2 pole GFEP breaker in branch
circuit breaker box upstream of the controller
2. Requirement shall not apply in industrial es-
tablishments where there is alarm indication of
ground faults and the following conditions apply:
a. conditions of maintenance and supervison
ensure that the qualified person(s) service the
installed heater.
b. continued circuit operation is necessary for
safe operation of equipment or process.