31
Address
Description
Range
Comments
40022
Parity
0-2
0 - NONE
1 - EVEN
2 - ODD
40023
Modbus Slave Address
0-255
Expressed as an integer number
40024
Reserved
40025
GFEP Alarm Threshold for
Ckt 1
30-150
Expressed as an integer number
(in mA e.g. 75 = 75mA)
40026
Low Current Alarm for
Ckt 1
0.0- 100.0
Expressed as an integer number in tenths of
Amp (e.g. 250 = 25.0 Amp)
40027
HI Current alarm for
Ckt 1
0.0 – 100.0
Expressed as an integer number in tenths of
Amp (e.g. 250 = 25.0 Amp)
40028
GFEP Alarm behavior Ckt 1
0-3
0 - Alarm Only, non latching
1 - Alarm and Trip, non latching
2 - Alarm and Trip, Latching
3 - Alarm Only, Latching
40029
Reserved
40030
GFEP Hi Alarm Threshold for
Circuit 2
30-150
Expressed as an integer number
(in mA e.g. 75 = 75mA)
40031
Low Current Alarm for
Circuit 2
1.0- 100.0
Expressed as an integer number in tenths of
Amp (e.g. 250 = 25.0 Amp)
40032
HI Current alarm for Circuit 2
0.0 – 100.0
Expressed as an integer number in tenths of
Amp (e.g. 250 = 25.0 Amp)
40033
Soft Start Circuit 1
0-1
0 - No
1 - Yes
40034
Soft Start Circuit 2
0-1
0 - No
1 - Yes
40035
GFEP Alarm behavior Ckt 2
0-3
0 - Alarm Only, non latching
1 - Alarm and Trip, non latching
2 - Alarm and Trip, Latching
3 - Alarm Only, Latching
40036
Temperature sensing
( Circuit 1)
0-4
0 - Controller will take the highest reading out of
two RTDs (1A and 1B)
1 - Controller will take the lowest reading out of
two RTDs (1A and 1B)
2 - Controller will take the average reading out
of two RTDs (1A and 1B)
3 - Controller will use RTD # 1A
4- Controller will use one RTD 1A to control both
circuits
40037
Temperature sensing (Circuit 2)
0-3
0 - Controller will take the highest reading out of
two RTDs (2A and 2B)
1 - Controller will take the lowest reading out of
two RTDs (2A and 2B)
2 - Controller will take the average reading out
of two RTDs (2A and 2B)
3 - Controller will use RTD # 2A
40038
Default output 1
0-100%
Expressed as an integer number (e.g. 75 = 75%)
40039
Default output 2
0-100%
Expressed as an integer number (e.g. 75 = 75%)
40040
Reserved
40041
Reserved