29
Description of Modbus Register Set
Modbus defines several function types; these instruments support the following types:
Table 1 - Modbus Function Code Set
Function Code
Function Name
03
Read Holding Registers
04
Read Input Registers
06
Write Single Holding Register
16
Write Multiple Holding Registers
Input Registers
Table 2 - ITC-FS 1&2 Circuit Input Registers
Address
Description
Comments
30000
Sensed Temperature Ckt 1
Sensed Temperature Circuitl 1
30001
Setpoint Ckt 1
Setpoint Circuit 1
30002
Sensed ground fault current on Ckt 1
Sensed ground fault current on circuit 1
30003
Sensed load on Ckt 1 (expressed as integer
number ion tenths of Amp e.g. 154 = 15.4 Amp)
Sensed load on circuit 1 (expressed as integer
number ion tenths of Amp e.g. 154 = 15.4 Amp)
30004
Control Output Command on Ckt 1
Control Output Command on Circuit 1
30005
Sensed Temperature on Ckt 2
Sensed Temperature on Circuit 2
30006
Setpoint circuit 2
Setpoint circuit 2
30007
Sensed ground fault current on Ckt 2
Sensed ground fault current on circuit 2
30008
Sensed load on Ckt 2 (expressed as integer
number ion tenths of Amp e.g. 154 = 15.4 Amp)
Sensed load on circuit 2 (expressed as integer
number ion tenths of Amp e.g. 154 = 15.4 Amp)
30009
Control Output Command on Ckt 2
Control Output Command on Circuit 2
30010
Sensed Ambient Temperature
Sensed Ambient Temperature
30011
Reserved
30012
Reserved
30013
Reserved
30014
Reserved
30015
Reserved
30016
Reserved
30017
Reserved
30018
Firmware ver CPU 1
30019
Firmware ver CPU 2