46
Table A
Modbus Function Code Set
Function
Code
Function Name
03
Read Holding Registers
04
Read Input Registers
06
Write Single Holding Register
16
Write Multiple Holding Registers
Detailed Register Descriptions are on the following
pages. See Table 1 & 2 for ITLS/ITAS 6 Registers and
Table 3 & 4 for ITLS/ITAS 2-4 Registers.
Description of Modbus Register Set
Input Registers
Channel outputs can be disabled through use of the discrete output register set.
Table 1: ITLS/ITAS 6-72 Circuit Input Registers
Input Register
Address
Name
Range
Format
300001
Temperature from Sensor 1
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300002
Temperature from Sensor 2
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300003
Temperature from Sensor 3
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300004
Temperature from Sensor 4
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300005
Temperature from Sensor 5
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300006
Temperature from Sensor 6
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300007
Temperature from Sensor 7
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300008
Temperature from Sensor 8
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300009
Temperature from Sensor 9
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300010
Temperature from Sensor 10
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300011
Temperature from Sensor 11
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300012
Temperature from Sensor 12
from -800 to 11000
expressed in tenth of deg e.g., 765 = 76.5˚F
300013
Temperature from Sensor 13
from -800 to 11001
expressed in tenth of deg e.g., 765 = 76.5˚F
300014
Temperature from Sensor 14
from -800 to 11002
expressed in tenth of deg e.g., 765 = 76.5˚F
300015
Temperature from Sensor 15
from -800 to 11003
expressed in tenth of deg e.g., 765 = 76.5˚F
300016
Temperature from Sensor 16
from -800 to 11004
expressed in tenth of deg e.g., 765 = 76.5˚F
300017
Temperature from Sensor 17
from -800 to 11005
expressed in tenth of deg e.g., 765 = 76.5˚F
300018
Temperature from Sensor 18
from -800 to 11006
expressed in tenth of deg e.g., 765 = 76.5˚F
300019
Temperature from Sensor 19
from -800 to 11007
expressed in tenth of deg e.g., 765 = 76.5˚F
300020
Temperature from Sensor 20
from -800 to 11008
expressed in tenth of deg e.g., 765 = 76.5˚F
300021
Temperature from Sensor 21
from -800 to 11009
expressed in tenth of deg e.g., 765 = 76.5˚F
300022
Temperature from Sensor 22
from -800 to 11010
expressed in tenth of deg e.g., 765 = 76.5˚F
300023
Temperature from Sensor 23
from -800 to 11011
expressed in tenth of deg e.g., 765 = 76.5˚F
300024
Temperature from Sensor 24
from -800 to 11012
expressed in tenth of deg e.g., 765 = 76.5˚F
300025
Temperature from Sensor 25
from -800 to 11013
expressed in tenth of deg e.g., 765 = 76.5˚F
Содержание IntelliTrace ITAS
Страница 4: ......