Definitions for each of the Load Setup Menu Input Cells
Load HI Stpt ................. High Current Alarm Limit (Amps)
LoadLO Stpt ................. Low Current Alarm Limit (Amps)
GFEP: ........................... Maximum Allowable Leakage Current setpoint (milliamps)
Trip (GFEP): .................. Enabled: If the GFEP limit is met, the output will be 0%.
Disabled: If the GFEP limit is met, the output is unaffected.
Latch (GFEP): ............... Enabled: If the GFEP limit is met, the alarm condition will remain until it is manually cleared.
Disabled: If the GFEP limit is met, the alarm condition will be cleared once the GFEP vari-
able is less than the GFEP setpoint
Apply Globally: ............. This allows the user to copy all of the settings or Circuit Parameters from Circuit #1 to all
other available Circuits.
Apply Settings Globally
The ITLS/ITAS has a feature which allows the user to apply settings from a single loop to all of the remaining loops
within the system. Within Loop #1 on the Setpoints Tab (See Figure 4), complete the input of the parameters and
select the “Apply Globally” button to mirror these settings across all loops.