background image

Chromalox

®

DIVISION  

4

                                      SECTION  

HVH

SALES 

REFERENCE 

DATE 

SERVICE REFERENCE

PF203-6

161-305679-001

JANUARY, 2012

(Supersedes PF203-5)

Installation, Operation 

and 

MAINTENANCE 

Type HVH Horizontal/Vertical Unit Heater

Heater Location Instructions:

Arrange units so their discharge air streams:

 

A.

  Are  subjected  to  a  minimum  of  interference  from  columns,  

machinery and partitions.

 

B.

  Wipe exposed walls without blowing directly at them.

 

C.

  Are directed away from room occupants in comfort heating.

 

D.

  Are directed along the windward side when installed in a build-

ing exposed to a prevailing wind.

 

E.

 See additional mounting limitations in Table D.

Locate thermostat on interior partition walls or posts away from 

cold drafts, internal heat sources and away from heater discharge air 

streams.

Small rooms can be heated by one unit heater. Where two walls 

are exposed, the heater should be mounted as shown in Figure 1.

Large rooms require multi-unit installation. Number and capacity 

of units will be determined by volume of building and square feet of 

floor area to be heated. Arrange units to provide perimeter air circula-

tion where each unit supports the air stream from another.

© 2012 Chromalox

®

, Inc.

Exposed

Exposed

Exposed

Exposed

Exposed

Exposed

Figure 1 - Single and Multi Unit Mounting

warning

Failure to understand and follow these installation instructions and 

the  “WARNING”  notes  therein  may  result  in  serious  personal  injury 

from electrical shock, or from the heater falling due to faulty installation.

This heater is not intended for use in hazardous atmo-

spheres where flammable vapors, gases, liquids or other 

combustible atmospheres are present as defined in the 

National  Electric  Code.  Failure  to  comply  can  result  in 

explosion or fire. For these applications see PDS CXH-A-

EP (PF490).

ELECTRIC SHOCK HAZARD. Disconnect all power before 

installing or servicing heater. Failure to do so could re-

sult in personal injury or property damage. Heater must 

be installed or serviced by a qualified person in accor-

dance with the National Electrical Code, NFPA 70. 

This heater is not intended for use in exposed outdoor, 

marine,  or  wash-down  environments  or  in  areas  where 

corrosive liquids or fumes exist under normal conditions.

ELECTRIC  SHOCK  HAZARD.  Any  installation  involving 

electric heaters must be performed by a qualified person 

and must be effectivley grounded in accordance with the 

National Electrical Code to eliminate shock hazard.

Do not mount mercury type thermostat directly on unit. Vibration 

could cause heater to malfunction.

The heater must be mounted at least 7’ above the floor to prevent 

accidental contact with the heating elements or fan blade which could 

cause injury.

Keep at least 5’ clearance in front of the heater. Refer to Table D 

for side, top and back clearance requirements.

general

Содержание HVH-02-21

Страница 1: ...to understand and follow these installation instructions and the WARNING notes therein may result in serious personal injury from electrical shock or from the heater falling due to faulty installation This heater is not intended for use in hazardous atmo spheres where flammable vapors gases liquids or other combustible atmospheres are present as defined in the National Electric Code Failure to com...

Страница 2: ...5 66 534 20 5 8 17 1 8 14 1 16 50A 1 14 HVH 20 63 600 19 500 3 18 8 66 534 20 5 8 17 1 8 14 1 16 50A 1 14 HVH 25 23 208 240 18 720 24 900 3 60 0 84 959 29 3 16 26 1 16 14 5 8 50A 2 15 HVH 25 43 480 25 000 3 30 2 85 300 29 3 16 26 1 16 14 5 8 50A 1 14 HVH 25 63 600 25 000 3 24 1 85 300 29 3 16 26 1 16 14 5 8 50A 1 14 HVH 30 23 208 240 22 400 29 900 3 72 1 102 019 29 3 16 26 1 16 14 5 8 50A 2 15 HVH...

Страница 3: ...ns In L1 L2 X 2 5 kW 3 8 16 2 7 8 7 1 8 3 3 4 7 1 2 20 kW 3 8 16 4 5 16 9 3 8 5 1 2 25 50 kW 3 8 16 8 15 16 14 9 15 16 Table D Clearance Requirements Vertical Discharge Model Mounting Limitations In Back to Wall Side to Wall Top to Ceiling HVH 02 Thru HVH 05 10 1 4 6 6 HVH 07 Thru HVH 20 13 6 6 HVH 25 Thru HVH 50 15 1 2 6 6 Horizontal Air Flow 1 Height above floor A In areas where ceiling height i...

Страница 4: ...bs Use With A B C M N U V W HVC 1 16 1 8 13 10 8 3 8 5 3 4 7 3 4 9 3 4 12 4 HVH 02 04 05 HVC 2 20 5 8 17 1 8 12 3 4 10 3 4 6 3 4 7 3 4 13 12 8 HVH 07 10 12 15 HVC 3 20 5 8 17 1 8 14 1 16 12 1 16 8 1 16 7 3 4 13 5 16 8 7 HVH 15 600V HVH 20 HVC 4 29 13 16 26 1 16 14 5 8 11 3 4 8 3 16 7 3 4 22 5 16 8 7 16 17 HVH 25 30 35 40 45 50 Figure 6 Optional Wall Swivel Mounting Bracket S R P Q T ADAPTOR BRACKE...

Страница 5: ...ctors and the joint should be then well insulated 3 Consult the local wiring code in your area SUMMER FAN SWITCH Refer to Instruction sheet PF205 with out relay PF206 with relay MOUNTED ON FRONT OF HEATER When the switch handle is pointing toward the Summer Fan ON position the fan will run continu ously When the switch handle is pointing toward the WINTER HEAT position the fan will run only when t...

Страница 6: ...switch built in or field installed Power 60 Hz Optional thermostat built in or field installed Blue Blue Motor Optional disconnect switch built in or field installed Power 60 Hz L1 L3 L2 T1 T3 T2 Purple Orange Pink C1 C3 C2 Remove jumper wire when thermostat is used Cutout Notes 1 Omit L3 wiring for 1ø heaters 3Ø Wiring Optional thermostat built in or field installed TO T1 TO T1 TO T2 TO T3 TO T3 ...

Страница 7: ... Delay Relay Transformer 40VA Built In or Remote Thermostat Termnal Block Control Refer to Nameplate for XFMR Primary Input and Seconday Control Voltage Line Fusing Line Fusing Built in or External Disconnect Switch Capacitor Fusing Alternate 1PH Motor Wiring Fusing Figure 14 Figure 15 Elements 3 Phase Wiring Optional Pliot Light Motor Contactor AR Cutout Time Delay Relay Transformer 80VA Built In...

Страница 8: ... 004 112 130367 002 HVH 10 23 7 5 10 208 240 3 118 305659 002 193 302912 004 112 130367 002 HVH 10 43 10 480 3 118 305659 003 193 302912 005 112 130367 002 HVH 12 83 12 5 208 3 118 305659 004 193 302912 004 112 130367 002 HVH 12 23 9 4 12 5 208 240 3 118 305659 005 193 302912 004 112 130367 002 HVH 12 43 12 5 480 3 118 305659 006 193 302912 005 112 130367 002 HVH 15 83 15 208 3 118 305659 007 193 ...

Страница 9: ... Contactor P N 072 306110 014 7 35 277V 35A Contactor P N 072 306110 019 7 35 277V 50A Contactor P N 072 306110 020 INTEGRAL THERMOSTAT 00 DISCONNECT SWITCH 0 00 No Thermostat 0 No Disconnect Switch TL SPST P N 300 049197 003 D 50A P N 292 303472 007 TL DPST P N 300 049197 004 D 80A P N 168 303598 007 TH SPST P N 300 049197 001 D 100A P N 168 303598 008 TH DPST P N 300 049197 002 PILOT LIGHT 0 OUT...

Отзывы: