Optional Wall Mount Kit

The DTS-HAZ may be mounted on vertical surfaces. To 

maintain UL/cUL and Class 1, Division 2 compliance, 

the user must use the optional Wall Mounting Bracket 

Kit (MP-2 DTS-HAZ Mounting Plate Kit, part number 

5120-13015).
Considerations:
1. The kit comes complete with two stainless steel 

mounting brackets and the necessary hardware to 

mount the brackets to the DTS-HAZ.

2.  Should the owner use other means to mount the 

DTS to a vertical surface, a minimum of 3 inches 

or 76 mm must be maintained from the rear of the 

DTS-HAZ to the mounting surface. This is neces-

sary to provide adequate airflow across the heat 

sink at the rear of the DTS.

3.  When installing the DTS on a vertical surface, the 

Pipe Standoff is not used and is typically replaced 

by rigid 1” NPT conduit. The conduit shall terminate 

into the Compression Fitting.

Ordering Information:
Wall Mount Kit PCN (Part Number): 318043

.657

 [16.69mm]

.875

 [22.23mm]

.875

 [22.23mm]

Ø

.390 [

Ø

9.91mm]

Ø

.218 [

Ø

5.54mm]

3.000

 [76.20mm]

RECOMMENDED - WALL MOUNT LAYOUT

MAXIMUM #10 STUD

Bracket Material:

16 ga Stainless Steel

0.059 " (1.5mm) nominal

7.750 [196.85mm]

4.500

 [114.30mm]

Содержание DTS-HAZ

Страница 1: ...1 Installation Instructions DTS HAZ DTS HAZ DC for use with Self Regulating Constant Wattage Mineral Insulated Electric Heating Cables PJ944 12 161 562581 049 April 2020 ...

Страница 2: ...2 ...

Страница 3: ...on Box 7 1 RTV 2 1 Line Ambient Sensing RTD 8 1 O Ring 3 1 Compression Fitting 9 1 Self Regulating Cable Grommet 4 1 Locknut 10 1 Constant Wattage Cable Grommet 5 1 Silicone Termination Boot 11 1 9 VDC Battery Connector 6 1 Pipe Standoff 12 1 Protective Sleeve 7 11 4 5 6 12 8 3 1 2 10 9 ...

Страница 4: ...nstallation The instal lation and proximity for the disconnect device must satisfy the electrical Authority having ju risdiction for the installation Branch circuit protection should be set for 40 amps or lower In all cases where the symbol is used on the product consult the documentation to find out the nature of the potential hazard and any ac tions to be taken General The DTS HAZ and DTS HAZ DC...

Страница 5: ...e adapter Chromalox model SPA not included is required 4 While bending the heating ca ble work the cable through the braid opening Pull the braid tight 2 Score the outer insulation 7 inches from the end of the cable Lightly cut the outer jacket up the center to the end of heating cable and remove the outer jack et from the cable WARNING DO NOT CUT METAL BRAID Note If using over braid only cable sk...

Страница 6: ... shall have the included protective sleeve slid over it once inside the enclosure Then insert grounding braid into grounding terminal Attach junction box cover to seal enclosure Access hole on right is designed for a 3 4 conduit hub Note The conduit hub shall be listed for Class 1 Div 2 Class II Div 1 2 Class III Div 1 2 and NEMA 4X rated by a nationally recognized testing laboratory For ATEX or I...

Страница 7: ...opri ate screw driver ONLY until snug It is recom mended that the lid be secured with a torque of 12 15 inch lbs per screw Overtightening or uneven tightening may cause the lid to break which would void all environmental and haz ardous location approvals Due to an electrical shock hazard do not operate thermostat if lid is cracked broken or uneven with enclosure Be sure to install this device vert...

Страница 8: ... mode d Deadband The allowable temperature differen tial between the Set Point and the Sensed Tem perature during normal operation The Deadband is centered on the Setpoint The Deadband has a range of 2 to 10 deg in 2 degree increments The Load is removed once the temperature is 1 2 way between the Setpoint and the upper limit of the Deadband e Temperature Units selection between degrees Fahrenheit...

Страница 9: ...DOWN MODE UP DOWN MODE UP DOWN MODE UP DOWN MODE UP DOWN SSrt UnIt bAnd LotP HItp StpT Troubleshooting Alarm Type Display Solution Sensor Open Sens err Check if your sensor is correctly connected to the unit Sensor Shorted Sens err Check if your sensor is correctly connected to the unit Lo Temperature Blinking between sensed temperature and LotP Sensed temperature is below Lo Temp Threshold Alarm ...

Страница 10: ...urface a minimum of 3 inches or 76 mm must be maintained from the rear of the DTS HAZ to the mounting surface This is neces sary to provide adequate airflow across the heat sink at the rear of the DTS 3 When installing the DTS on a vertical surface the Pipe Standoff is not used and is typically replaced by rigid 1 NPT conduit The conduit shall terminate into the Compression Fitting Ordering Inform...

Страница 11: ... a 0 125 Amp 350 VAC 2AG fuse Maximum RTD output 1 25 volts 7 milliamps Temperature Rating UL T4a IEC ATEX T4 Protection IP66 Settings Setpoint 80 F to 1100 F 62 C to 593 C Alarms High temp to 1150 F 621 C Low temp to 80 F 62 C Deadband 2 F or C to 100 F or C 1 to 50 around the setpoint Alarm Function Mode Default Optional Normal Operation Closed Open Alarm Condition Open Closed Power Off Open Ope...

Страница 12: ...e Chromalox limited warranty applicable to this product at http www chromalox com customer service policies termsofsale aspx 2016 Chromalox Inc All rights reserved Chromalox 103 Gamma Drive Pittsburgh PA 15238 412 967 3800 www chromalox com ...

Отзывы: