Chromalox Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
5
3.
You will be prompted for a password. The password was set in example, to be
1111. Enter 1111 and press Enter. If any other password is entered, except the
Master Password, the Configuration menu will not be accessed
4.
Select 2. “Configuration”, and then Enter.
5.
You will see the prompt to enter the password. Enter 1111 and press enter. You
will then enter the configuration menu.
6.
Select 2. “Change Program”, and then Enter.
7.
Change “Output 1” to “Y”, so Output 1 will now be reverse acting. Then press
Enter.
8.
Change from “C” to “F”, then press Enter.
9.
Set Zone to “Any”, then press Enter.
10.
Set “Alarm Silence” to 1 minute, then press Enter.
11.
Set “If an input fails” to “Sound Alarm”, then press Enter.
12.
Set “Zone 1” to the input type that has been connected to Zone 1 on the
controller, then press Enter.
13.
Set “Zone 1 Trip 1:” to 65º F, then press Enter.
14.
Set “Zone 1 Trip 1: Trip Over or Under” to “Under”, then press Enter.
15.
Set “Zone 1 Trip 1: Sound Alarm on trip” to “Yes”, then press Enter.
16.
Set “Zone 1 Trip 1: Outputs to trip:” to “Output1:Y” and the other outputs leave as
N, then press Enter.
17.
Set “Zone 1 Trip 1: Untrip Outputs by” to “Using Hysteresis”, then press Enter.
18.
Set “Zone 1 Trip 1: Set Hysteresis:” to “5”, then press Enter.
19.
The display will read “Zone 1 Trip 2: Off”. Press & hold Enter until CX224 re-
initializes.
20.
The current temp reading will now be displayed on the controller for Zone 1.
21.
Cool sensor until alarm and output trip. (Put sensor in a freezer or place sensor in a
bag and place in cold water).