Chromalox Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
3
8.
Select “Program Password”, and press Enter.
9.
Enter 1111 for password by using the up arrow and right arrow. This will enable
password protection for the “Configuration Menu” option, in the main menu.
10.
Press Back to exit one menu level.
11.
Select 2. “Configuration”, and then Enter.
12.
You will see the prompt to enter the password. Enter 1111 and press enter. You
will then enter the configuration menu.
13.
Select 2. “Change Program”, and then Enter.
14.
Leave all outputs set to N for “Reverse Acting outputs?”, this will cause all outputs
to be direct acting. Press Enter.
15.
Set “Temperature Scale” to “F” for degrees Fahrenheit, by using the up arrow, then
press Enter.
16.
Set “Zone to be displayed during normal operation” to “Any”, then press Enter.
This will allow the user to choose the zone that will be displayed on the CX224.
17.
Set “Minutes of Alarm Silence when a key is pressed” to 1 minute, then press Enter.
This will cause the alarm to resound 1 minute after the output has been tripped, if
the current reading is still above the trip setting.
18.
Set “If an input fails” to “Sound Alarm”, then press Enter. This will cause the alarm
to sound if the input fails.
19.
Set “Zone 1 Choose input type:” to the input type that has been connected to
Zone 1 on the controller, then press Enter.
20.
Set “Zone 1 Trip 1:” to 85º F, then press Enter.
21.
Set “Zone 1 Trip 1: Trip Over or Under” to “Over”, then press Enter.
22.
Set “Zone 1 Trip 1: Sound Alarm on trip” to “Yes”, then press Enter.
23.
Set “Zone 1 Trip 1: Outputs to trip:” to “Output1:Y” and the other outputs leave as
N, then press Enter.
24.
Set “Zone 1 Trip 1: Untrip Outputs by” to “Using Hysteresis”, then press Enter.
25.
Set “Zone 1 Trip 1: Set Hysteresis:” to “5”, then press Enter.
http://www.chromalox.com