B) Program
Using the keypad to configure the CX224, use the Setup Worksheet provide in the
manual to speed up the process and reduce errors. Due to the 60-second timeout in
the CX224, it is best to fill out the Setup Worksheet before configuring the unit. This
will also allow you to have record of the settings that are programmed into the unit for
future reference.
A description for each of the configuration options is give on the following pages.
Reverse acting outputs?
- Choose the outputs you would like to configure for reverse
action.
N – Relay: Normally Open (NO) contact will be open and the Normally Closed (NC)
contact will be closed.
Logic: Output will be low (0V) in untripped state.
Y – Relay: NO contact will be closed and the NC contact will be open in the untripped
state. The Logic: Output will be high (+5V) in untripped state.
Temperature Scale:
- Choose the temperature scale that the CX224 should use. RTDs
and thermocouples will use this temperature scale for display. Options are F,
Fahrenheit and C, Celsius.
Zone to be displayed during normal operation:
- Choose how the input readings
should be displayed.
The user can always adjust the displayed reading by pressing keys, after 5 seconds the
CX224 will resume it’s process of displaying the High, Low or Scanning through inputs.
High – Highest input reading is displayed, regardless of input type.
Low – Lowest input reading is displayed, regardless of input type.
Any – Display will stay on the zone that the user has set it to.
Minutes of alarm silence when a key is pressed: -
Set the amount of time to wait
until the alarm will resound, if the alarm condition is still present. Valid range is 1 to
100 minutes or Stays Off. This setting only resounds the alarm, it will not re-trip an
output. It is designed to remind personnel that there is still a trip condition in affect
.
If an input fails:
- This setting allows the user to determine what action the CX224
should take if a broken sensor is detected.
Sound alarm – Alarm will sound if input fails. Alarm will resound according to the
“Minutes of alarm silence when a key is pressed” set in the previous step.