background image

Chromalox

®

DIVISION  

4

                                      SECTION  

CVEP

SALES

REFERENCE

DATE

SERVICE REFERENCE

Installation, Operation 

and

RENEWAL PARTS IDENTIFICATION

PF457-8

JUNE, 2010

(Supersedes PF457-7)

161-302639-001

GENERAL

INSTALLATION

NOTICE: Carefully remove heater from carton and check for
shipping damage. Any damage claims should be entered
immediately with the carrier.

Type CVEP Convection Heaters are designed for use in Class

I, Div I hazardous environments. Units without control options
are suitable for areas classified as Groups B, C & D. Units with
built-in controls can be supplied for groups C and D or B, C and
D. Refer to classification stamped on heater nameplate.

FIRE/EXPLOSION HAZARD. 

To prevent ignition of haz-

ardous atmospheres, this heater should not be installed in
areas where vapors or gases having an ignition tempera-
ture less than 280˚C (536˚F)(T2A) at 1.8kW, 3.6kW, 4.5kW,
7.6kW, 9.0kW or 180˚C (356˚F)(T3A) at 1.6kW, 3.2kW,
4.0kW are present.
These heaters must not be operated in ambient tempera-
tures exceeding 40˚C (104˚F).

1.

Connect air heaters to the same line voltage as on heater nameplate.

2.

Heaters can be mounted individually end to end.

3.

Heaters can be mounted directly on any type of surface masonry,
concrete, block, plastered walls, metal framework, etc.-using
appropriate hardware.

4.

All controls such as thermostat and contactor, when required must

have the same explosion-proof rating as heater.

5.

Do not install one unit above the other.

6.

Units are mounted a minimum of 8” above the floor.

7.

Heaters are mounted on wall in a horizontal position with termi-
nal end at right. 

Never

recess heater into wall.

8. NOTE:

Article 500 of the National Electric Code (NEC) out-

lines requirements for installation of electrical equipment in haz-
ardous (Classified) locations.

9.

All unit electrical installation fittings, conduit, wiring and seals
must meet NEC and local codes for hazardous locations. External
line fusing or circuit breaker protection is required.

10.

Failure to understand and follow these installation instructions
and the “WARNING” notes contained therein may result in
severe personal injury, death or substantial property damage.

E L E C T R I C   S H O C K   H A Z A R D .   A n y   i n s t a l l a t i o n
involving electric heaters must be performed by a
qualified person and must be effectively grounded
in accordance with the National Electrical Code to
eliminate shock hazard.

ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do so
could result in personal injury or property damage.
Heater must be installed by a qualified person in accor-
dance with the National Electrical Code, NFPA 70.

1.

Remove front panel by removing screws.

2.

Locate desired heater position on wall.

3.

Locate mounting holes for rear panel. Rear panel must be a mini-
mum of 8” from the floor.

4.

Refer to Figure 1A, 1B or 1C for mounting hole layout for each
cabinet size.

5.

Drill a pilot hole in wall mounting surface at each mounting hole
location. Use a convenient small size drill.

6.

Drill the mounting holes in accordance with size in Table 1. Insert
anchors where applicable.

7.

Fasten rear panel to wall with screws noted in Table 1.

8.

Replace front panel and screws.

FIRE HAZARD. Never operate heater with front panel
off. Adequate air flow across heating elements
requires the front panel to be in place. The heating
elements could overheat causing equipment damage
or personal injury.

Type CVEP-C

Convection Air Heater for Hazardous Locations

© 2010  Chromalox, Inc.

Содержание CVEP-C

Страница 1: ...of the National Electric Code NEC out lines requirements for installation of electrical equipment in haz ardous Classified locations 9 All unit electrical installation fittings conduit wiring and seals must meet NEC and local codes for hazardous locations External line fusing or circuit breaker protection is required 10 Failure to understand and follow these installation instructions and the WARNI...

Страница 2: ...Types and Sizes If clearance permits use washer lockwasher and nut otherwise drill and tap to these lengths add thickness of beam washers nut etc If mounting structure permits Except plastered hollow walls explosive type anchors can be used Suggested size noted in Table and or sketches be used to determine size of anchors Select overall length of screw to provide a minimum penetration of 1 inch in...

Страница 3: ...ent and should install adequate back up controls and safety devices with their electric heating equipment Where the conse quences of failure could result in personal injury or property damage back up controls are essential 1 Do not operate heater at voltages in excess of that stamped on the heater since excess voltage will shorten heater life and cause high element temperatures which may exceed al...

Страница 4: ...ensure terminal cover is tightly closed before energiz ing 4 Sealed Heavy duty Finned Element assembly Explosion Proof Junction Box for Field wiring Mounting Holes ELEMENT REPLACEMENT ELECTRIC SHOCK HAZARD Disconnect all power before installing or servicing heater Failure to do so could result in personal injury or property dam age 1 Disconnect power from circuit 2 Remove cover from junction box a...

Страница 5: ...00 45 4 5 T2A 536 280 15 350 76 7 6 T2A 536 280 25 930 90 9 0 T2A 536 280 30 700 Code Voltage Maximum kW Allowable 1 120 1 8 2 240 9 0 3 380 9 0 4 480 9 0 5 415 9 0 6 575 9 0 7 277 9 0 8 208 9 0 9 600 9 0 Code Phase 1 1Ø 3 3Ø Not available in 120 277V Control Combination Code Contactor Transformer Coil Secondary 00 None None 30 24 Volt 24 Volt 31 24 Volt None 32 120 Volt 120 Volt 33 120 Volt None ...

Страница 6: ...Model Width A Height B Depth C Wt Lbs Element P N Qty 1 8 3 6 6 150 12 300 208 1 8 7 17 3 CVEP C 18 36 81 34 20 1 16 8 15 16 46 58 003 304650 034 1 or 2 1 8 3 6 6 150 12 300 208 3 5 0 10 0 CVEP C 18 36 83 34 20 1 16 8 15 16 46 58 003 304650 038 1 or 2 1 8 3 6 6 150 12 300 240 1 7 5 15 0 CVEP C 18 36 21 34 20 1 16 8 15 16 46 58 003 304650 098 1 or 2 1 8 3 6 6 150 12 300 240 3 4 3 8 7 CVEP C 18 36 2...

Страница 7: ...y 00 None None 30 24 Volt 24 Volt 31 24 Volt None 32 120 Volt 120 Volt 33 120 Volt None 34 208 240 Volt None 35 277 Volt None Primary Secondary Transformer Voltage Voltage 208 240 480 24 315 304252 002 208 240 480 120 315 304252 001 277 24 315 304252 004 575 24 315 304252 005 277 575 120 315 304252 003 Code Thermostat 00 None 40 300 049197 003 42 300 113075 003 Contactor Coil Voltage 30 Amp 50 Amp...

Страница 8: ...84404 Phone 1 800 368 2493 www chromalox com 02 074 TA Q4 EF Litho in U S A Limited Warranty Please refer to the Chromalox limited warranty applicable to this product at http www chromalox com customer service policies termsofsale aspx ...

Отзывы: