Chromalox CHS-1080 Скачать руководство пользователя страница 2

2

High Pressure
Control

Pressure
Gauge

Manual Reset
Pressure Conrol

Electric
Control
Box

Blow Down
Drain Valve
(L)

Return
Inlet (J)

Heating
Elements

Step Sequencer
(Optional)

Wall

30”

C

B

A

Wall

D

I

H

E

Blow Down
Drain Valve (L)

Check Valve
Water Inlet (K)

Water
Level
Control

G

60”

Safety
Valve (G)

Steam
Outlet (F)

INSTALLATION (cont’d.)

Figure 1

Figure 2

Figure 3

Model Number

A

B

C

D

E

F*

G

H

I

J

K

L

CHS-150 thru CHS-300

57”

45”

32”

40”

68”

3” NPT

1”

25”

31”

2” NPT

1” NPT

1” NPT

CHS-360 thru CHS-420

57”

45”

32”

40”

68”

4”

1”

25”

31”

2” NPT

1” NPT

1” NPT

CHS-495 thru CHS-630

57”

45”

32”

47”

86”

4”

1”

34”

40”

2” NPT

1” NPT

1” NPT

CHS-720 thru CHS-810

76”

58”

45”

47”

94”

6”

1-1/2”

38”

44”

2” NPT

1” NPT

1” NPT

CHS-945 thru CHS-1080

76”

68”

45”

47”

94”

6”

1-1/2”

38”

44”

2” NPT

1” NPT

1” NPT

CHS-1215 thru CHS-1620

86”

76”

56”

50”

98”

6”

1-1/2”

40”

46”

2” NPT

1-1/2” NPT

1” NPT

*CHS- thru 1620 have 2 control boxes (See Figure 2). Add 13” to “B” dimension.

*4” and 6” are flanged.

Safety

Valve

Globe

Valve

Insulated Steam Lines

(Pitch Down 5˚)

Water/Steam

Separator

Gate

Valve

Heat

Exchanger

Gate

Valve

Trap

Trap

(Typical Load)

Check Valve

Check Valve

Check

Valve

Vacuum

Breaker

Drain

Boiler

Auxiliary

Inlet

Cold Water

(for Initial Fill)

Pitch Down 5˚

Vent

Condensate

Return

Return

Cold Water

Make-Up

Strainer

Drain

Centrifugal

Turbine Pump

Typical Plumbing Installation of a Steam Boiler with Condensate Return System

Содержание CHS-1080

Страница 1: ...t Boilers INSTALLATION CAUTION To avoid electrical shock hazard boilers must be suitably grounded to earth NOTE Chromalox boilers are pre tested before shipment no internal piping or wiring is necessa...

Страница 2: ...34 40 2 NPT 1 NPT 1 NPT CHS 720 thru CHS 810 76 58 45 47 94 6 1 1 2 38 44 2 NPT 1 NPT 1 NPT CHS 945 thru CHS 1080 76 68 45 47 94 6 1 1 2 38 44 2 NPT 1 NPT 1 NPT CHS 1215 thru CHS 1620 86 76 56 50 98...

Страница 3: ...ety feature that prevents a dangerous situ ation should a contactor or relay stick Activation of the shunt trip device will completely disconnect the boiler from the power sup ply See Figure 7 3 Since...

Страница 4: ...Groups To Other Heater Groups Typical 3 Phase Heater Group To Power Curcuit Relay Step Sequencer Figure 9 Power Circuit Detail Low Water Probe 120 Volt Control Voltage Hi Limit Control Electronic Resi...

Страница 5: ...he other is used as a high limit control To deter mine the difference in the controls the high limit has a manual reset lever on top of the case Also there is no differential scale present 2 On all co...

Страница 6: ...sure Do not push reset until boiler has filled with water The use of chemical boiler cleaning compounds in these boilers voids all warranties unless approved by manufacturer Some compounds will damage...

Страница 7: ...ated on the inside of the control panel to boiler normal if the boiler is to be shut down each night Set it to 24 hour duty if the boiler is to remain on continuously 24 hours per day except during bl...

Страница 8: ...of the controlled medium will cause a change in the number of elements energized to compensate for it thus keeping the pressure constant This process is called modula tion PROPORTIONAL PRESSURE CONTR...

Страница 9: ...boiler off remove wiring from pressure control on sequencer low voltage terminal board 2 Turn on boiler to supply the voltage to sequencer Short terminal R and B for counter clockwise rotation and ter...

Страница 10: ...gized for safety When power resumes the control will re stage the loads one at a time Refer to the diagram for visual description of progressive sequencing PROGRESSIVE SEQUENCING The solid state seque...

Страница 11: ...nge 5 Thoroughly clean boiler flange of all foreign material Be certain no part of old gasket remains on boiler flange 6 Apply Slic Tite Gasket Compound or equal to both surfaces of new gasket supplie...

Страница 12: ...amp 128 118530 003 Power Circuit Fuse Class J 100 amp 128 118530 004 Valves and Gauges Description Part Number Pressure Gauge 3 1 2 160 344 118529 024 Gauge Glass Assembly 347 118537 002 Sight Glass 3...

Отзывы: