Installation, Operation

RENEWAL PARTS IDENTIFICATION

Horizontal Electric Steam Boiler

Model Number CHS 0 – 150 PSI

© 2010 Chromalox, Inc.

Power CC

Size of

Output

Nominal

90˚C

Amps

Standard Lbs. per

Model

B.H.P.

Fuse Delta

Size

Wire

per

Elements

Control

Hr. at

Number

Rating kW Contactors Size

kW

(Amps)

(M.C.M) Circuit

(kW)

System

212˚F

CHS-150*

15.3

150

5

50A 60A

30

1

300

4/0

181

2

60

452

1

30

CHS-180*

18.4

180

6

50A 60A

30

1

300

250

217

3

30

543

CHS-210*

21.4

210

7

50A 60A

30

1

600

600

253

3

60

633

1

30

CHS-240*

24.5

240

8

50A 60A

30

1

600

400

290

4

60

723

CHS-270*

27.6

270

9

50A 60A

30

1

600

600

326

4

60

814

1

30

CHS-300*

30.6

300

10

50A 60A

30

1

600

600

362

5

60

904

CHS-360

36.7

360

12

50A 60A

30

2

300

250

217

2

90

1085

3

60

CHS-420

42.9

420

14

50A 60A

30

2

600

350

254

4

90

1266

1

60

CHS-495

50.5

495

11

60A 100A

45

2

600

500

297

3

135

1492

1

90

CHS-540

55.1

540

12

60A 100A

45

2

600

600

324

4

135

1628

CHS-630

64.3

630

14

60A 100A

45

2

600

700

378

4

135

1889

1

90

CHS-720

73.5

720

16

60A 100A

45

3

600

400

324

5

135

2170

1

45

CHS-810

82.7

810

18

60A 100A

45

3

600

600

324

6

135

2441

CHS-945

96.4

945

21

60A 100A

45

3

600

700

378

7

135

2848

CHS-1080 110.0 1080

24

60A 100A

45

4

600

500

324

8

135

3255

CHS-1215 124.0 1215

27

60A 100A

45

4

600

700

378

9

135

3662

CHS-1350 138.0 1350

30

60A 100A

45

5

600

600

324

10

135

4069

CHS-1485 152.0 1485

3

60A 100A

45

5

600

700

378

11

135

4476

CHS-1620 165.0 1620

36

60A 100A

45

6

600

600

324

12

135

4883

Specifications — 480 Volt Boilers*

INSTALLATION

CAUTION: To avoid electrical shock hazard, boilers
must be suitably grounded to earth.

NOTE: Chromalox boilers are pre-tested before shipment; no internal
piping or wiring is necessary. 

WARNING:

Substitution of compo-

nents or modification of wiring without prior consent of Chromalox,
Inc. voids warranty.

1.

Locate unit on level floor or platform. 

NOTE:

A minimum dis-

tance of 60 inches from wall, other equipment, etc. must be
allowed for removal of the elements.

2.

Complete all piping to boiler. Connect water line to tagged fitting
on the motor and pump assembly, if used, or to tagged fitting on
water control feeder.

3.

When any type of feed other than a pump feed is used – the exist-
ing water supply must be 10 pounds greater than the boiler operat-
ing pressure to assure water supply maintains proper water level in
boiler. Otherwise, lack of water can cause heater failure. Keep feed
water line valves open at all times.

4.

All water feed systems are connected to supplied water inlet check
valve.

5.

Connect steam line (with Globe valve) to boiler steam outlet. Valve
should be placed as close as possible to boiler outlet.

6.

To insure maximum efficiency of supplied kw, all piping from out-
let should be insulated.

7.

Drain and relief valve piping should be in accordance with state
and local codes.

CHS-360 Steam Boiler

*150 kW Thru 300 kW Boilers available in 280V and 240V. Check Factory

Boiler Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Circuit Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Model No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. of Power Circuits . . . . . . . . . . . . . . . Amps. . . . . . . . . . . . . . . . . . . . 

Electrical Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Circuit Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

National Board No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Total Amps . . . . . . . . . . . . . . . Phase . . . . . . . . . . . . Cy . . . . . . . . . . . . . 

IMPORTANT – This data file contains the National Board Registration Certificate approving your generator. It must be kept near the generator at all times.

2 P’TROLS

3

P’TROLS

SEQUENCER

Содержание CHS-1080

Страница 1: ...t Boilers INSTALLATION CAUTION To avoid electrical shock hazard boilers must be suitably grounded to earth NOTE Chromalox boilers are pre tested before shipment no internal piping or wiring is necessa...

Страница 2: ...34 40 2 NPT 1 NPT 1 NPT CHS 720 thru CHS 810 76 58 45 47 94 6 1 1 2 38 44 2 NPT 1 NPT 1 NPT CHS 945 thru CHS 1080 76 68 45 47 94 6 1 1 2 38 44 2 NPT 1 NPT 1 NPT CHS 1215 thru CHS 1620 86 76 56 50 98...

Страница 3: ...ety feature that prevents a dangerous situ ation should a contactor or relay stick Activation of the shunt trip device will completely disconnect the boiler from the power sup ply See Figure 7 3 Since...

Страница 4: ...Groups To Other Heater Groups Typical 3 Phase Heater Group To Power Curcuit Relay Step Sequencer Figure 9 Power Circuit Detail Low Water Probe 120 Volt Control Voltage Hi Limit Control Electronic Resi...

Страница 5: ...he other is used as a high limit control To deter mine the difference in the controls the high limit has a manual reset lever on top of the case Also there is no differential scale present 2 On all co...

Страница 6: ...sure Do not push reset until boiler has filled with water The use of chemical boiler cleaning compounds in these boilers voids all warranties unless approved by manufacturer Some compounds will damage...

Страница 7: ...ated on the inside of the control panel to boiler normal if the boiler is to be shut down each night Set it to 24 hour duty if the boiler is to remain on continuously 24 hours per day except during bl...

Страница 8: ...of the controlled medium will cause a change in the number of elements energized to compensate for it thus keeping the pressure constant This process is called modula tion PROPORTIONAL PRESSURE CONTR...

Страница 9: ...boiler off remove wiring from pressure control on sequencer low voltage terminal board 2 Turn on boiler to supply the voltage to sequencer Short terminal R and B for counter clockwise rotation and ter...

Страница 10: ...gized for safety When power resumes the control will re stage the loads one at a time Refer to the diagram for visual description of progressive sequencing PROGRESSIVE SEQUENCING The solid state seque...

Страница 11: ...nge 5 Thoroughly clean boiler flange of all foreign material Be certain no part of old gasket remains on boiler flange 6 Apply Slic Tite Gasket Compound or equal to both surfaces of new gasket supplie...

Страница 12: ...amp 128 118530 003 Power Circuit Fuse Class J 100 amp 128 118530 004 Valves and Gauges Description Part Number Pressure Gauge 3 1 2 160 344 118529 024 Gauge Glass Assembly 347 118537 002 Sight Glass 3...

Отзывы: