P01 - Temperature set point
Move DIP switch S1 located on the side of thermostat to ON position.
“P01” and the temperature set point will appear on display.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: 14…77°F / -10…+25°C, Default: 37°F / 3°C
As long as the ambient temperature is lower than the temperature
set point P01, the Chroma-FP-OD will turn ON.
Pg. 9
Technician settings
Use the technician settings mode to view and adjust the following parameters:
Disconnect power and open the internal door by releasing the two screws.
Move DIP switch S1 located on the side of thermostat to ON position.
Press the [SELECT] and [+] buttons simultaneously to move forward to the next
technician parameter.
Press the [SELECT] and [-] buttons simultaneously to return to the previous
technician parameter.
Enter technician settings mode
Enter technician
settings mode
Important: Changes made to technician parameters will not take effect as
long as DIP switch S1 is in ON position.
Save changes
and exit
technician
settings mode
Parameters:
Save changes and exit technician settings mode
Move DIP switch S1 located on the side of thermostat to OFF position.
Temperature
set point
P01
Temperature set point
P02
Lower ambient temperature limit to stop
the heater
P03
Time delay before stopping the heater
P04
ON time for manual mode
P05
Heaters cycle time / Splitting time
P06
Enable/Disable 2
nd
temperature sensor
logic (Aquastat)
P08
MAC Address for BMS
and for Master-Slaves
P09
Commissioning / Test mode
P11
Master/Slave
P15
Temperature sensor calibration Offset
Restore defaults
Chroma-FP-OD Series
Owner’s manual & Technician Settings