74
OUTPUTS (400 to 600A Models)
OUT1, …, OUT3 Heat Control Connected Directly to Static Units
Function
Configurable (default: heat control)
State of control is displayed by LED (O1, O2,O3)
OUT1 is connected to Master unit,
OUT2 and OUT3 are connected to Expansion units
OUT5,...,OUT8 Cooling Control Outputs (Option)
Function
Configurable
Relay
Contact NO 3A, 250V/30Vdc cos
f
=1
Analog
0/2…10V (default), max 25mA short circuit protection
0/4…20mA, max. load 500ohm
isolation 500V
Resolution: 12 bit
Accuracy: 0.2% fs
Logic
24Vdc, > 18V a 20mA
Triac
230V/ max 4A AC51 (1A for each channel)
OUT9, OUT10 Alarm
Function
Function Configurable (default alarms)
Relay
Contact in exchange (C, NO, NC) 5A, 250V/30Vdc cos
f
=1
COMMUNICATIONS PORTS (400 to 600A Models)
PORT CFW-OP
Function
Serial comunication for KB-ADL terminal to display parameter
programming
PORT 1 Always Present
Function
Function Local serial communication
Protocol
ModBus RTU
Baudrate
Settable 1200,…,115200, (default 19,2Kbit/s)
Node address
Node address Settable with rotary-switches
Type
RS485 - isolation 1500V, double connector RJ10 telephone type 4-4
PORT2 (Fieldbus option)
Function
Fieldbus serial communication
Protocol
ModBus RTU, type RS485, baudrate
1200...115000Kbit/s
CANOpen 10K…1Mbit/s
DeviceNet 125K…0,5Mbit/s
Profibus DP
9,6K...12 Mbit/s
Ethernet Modbus TCP
10/100Mbit/s
Ethernet IP
10/100Mbit/s
EtherCAT 100Mbps
Содержание CFW
Страница 2: ...ii...