69
OUTPUTS (40 to 300A Models)
OUT1, …, OUT3 Heat Control Connected Directly to Solid-State Units
Function
Configurable (default: heat control)
State of control is displayed by LED (O1, ,O3)
OUT1 is connected to Master unit,
OUT2 and OUT3 are connected to Expansion units
OUT5,...,OUT8 Cooling Control Outputs (Option)
Function
Configurable (default: cooling control)
Relay
Contact NO 3A, 250V/30Vdc cos
f
=1
Continuous
0/2…10V (default), max 25mA short circuit protection
0/4…20mA, max. load 500ohm
isolation 500V
Logic
24Vdc, > 18V a 20mA
Triac
230V/ max 4A AC51 (1A for each channel)
OUT9, OUT10 Alarm
Function
Function Configurable (default alarms)
Relay
Contact NO 5A, 250V/30Vdc cos
f
=1
COMMUNICATIONS PORTS (40 to 300A Models)
PORT CFW-OP
Function
Serial comunication for KB-ADL terminal to display parameter
programming
PORT 1 Always Present
Function
Function Local serial communication
Protocol
ModBus RTU
Baudrate
Settable 1200,…,115200, (default 19,2Kbit/s)
Node address
Node address Settable with rotary-switches
Type
RS485 - isolation 1500V, double connector RJ10 telephone type 4-4
PORT2 (Fieldbus option)
Function
Fieldbus serial communication
Protocol
ModBus RTU, type RS485, baudrate
1200...115000Kbit/s
CANOpen 10K…1Mbit/s
DeviceNet 125K…0,5Mbit/s
Profibus DP
9,6K...12 Mbit/s
Ethernet Modbus TCP
10/100Mbit/s
Ethernet IP
10/100Mbit/s
EtherCAT 100Mbps
POWER (SOLID-STATE RELAY) (40 to 300A Models)
CATEGORY OF USE
(Tab. 2 EN60947-4-3)
AC 51 resistive or low inductance loads
AC 55b short wave infrared lamps (SWIR)
AC 56a transformers, resistive loads with high temperature coefficient
Trigger Mode
PA - Load management by adjusting the firing angle (only
configuration single-phase or delta open)
ZC - Zero Crossing with constant cycle time (settable in range
1-200sec)
BF - Burst Firing, or D.O.T. with variable cycle time optimized min.
HSC - Half Single Cycle corresponds to Burst Firing that includes ON
and OFF half-cycles.
Useful for reducing flicker with short-wave IR loads (applied only to
single-phase resistive or 3-phase 6-wire open delta loads).