11. Technical Characteristics
INPUTS (40 to 300A Models)
INA Analog Control Inputs
Function
Acquisition of % value for power control
Voltage
Linear: 0,…,5Vdc, Ri>100Kohm
Linear: 0,…,10Vdc, Ri>100Kohm
Current
Linear: 0/4…20mA, Ri =125ohm
Potentiometric
1, ..., 10Kohm, max 10mA from 5Vdc power CFW
IN1 Analog Process Inputs (Option)
Function
Acquisition of process variable
Max. error
0,2% f.s. ± 1 scale point at @ 25°C
Thermal drift
< 100 ppm/°C of f.s.
Sampling time
60 ms
Thermocouple Tc (ITS90)
J,K,R,S,T (IEC 584-1,CEI EN 60584-1, 60584-2)
Error cold junction comp. 0,1°/°C
Resistance thermometer RTD (ITS90)
Pt100 (DIN 43760)
Max line resistance
20ohm
Voltage
Linear: 0,…,60mV, Ri>1Mohm
0,…,1V, Ri>1Mohm
a 32-segment custom linearization can be inserted
Current
Linear: 0/4…20mA, Ri = 50ohm
a 32-segment custom linearization can be inserted
Line Voltage Measurement, Current /Voltage (optional) on Load
RMS line current measurement function
Line voltage read 50-60Hz; voltage in range:
90...530Vac for model with work voltage range 480Vac
90...660Vac for model with work voltage range 600Vac
90...760Vac for model with work voltage range 690Vac
Accuracy RMS voltage measurement
1% f.s. with neutral connected, 2% f.s. without neutral
RMS current measurement function
Load Current Read
Accuracy RMS current measurement
2% f.s. @25°C in start mode ZC e BF; in mode PA 2% f.s. with con-
duction angle >90°, 4% f.s. with conduction angle <90°
Function voltage measurement RMS on
load
Load voltage read
Accuracy RMS voltage measurement
on load
1% f.s. with VLOAD option measurement, (Otherwise, the value is
calculated from the values of line voltage and power delivered; ac-
curacy 2% F.S.)
Thermal drift for measure tension and
current in the load, tension of line
<0,02%/°C
Current and Voltage sampling time
0,25 ms
INDIG1,…,INDIG3 Digital inputs
Function
Configurable (default: disabled)
Only for INDIG3: PWM input (100Hz/0,03Hz) to check the %
value of power which depends on the cycle; this function lets
you to set a power set point by means of a digital signal (ex.
from PLC or controller with PWM output).
Type
5-30Vdc, 7mA isolation 1500V