5.1 Cleaning/Checking or Replacing the Fan – 40 to 300A Models
Periodic CleaningEvery 6-12 months (de-
pending on the dust level of the installation)
blow a compressed air jet downward
through the upper rectangular cooling grilles (on the
side opposite the fan). This will clean the internal heat
dissipater and the cooling fan.
IN CASE OF OVERHEAT ALARM:
If periodic cleaning does not eliminate the problem, do
as follows:
1. Remove the fan support grille by detaching the two
support tabs
2. Disconnect the fan connector from the board
3. Check the condition of the fan
4. Clean or replace the fan
Attention: check that the arrow (on the fan) indi-
cating the direction of air flow is pointing to the
heat sink
5. Insert the connector into the board
6. Insert the fan support grille until it attaches
7. Power up the device and check fan rotation when at
least one load is on
Fan Air
Direction
1
Fan
2
Lower Grill (Ventilation Intake)
3
Detail of insertion of fan connector in PCB