12
400 to 600A Models
Table 1: EMC Emission
AC semiconductor motor controllers and conductors
for non-motor loads
EN 60947-4-3
Emission enclosure compliant in firing mode single
cycle and phase angle if external filter fitted
EN 60947-4-3, CISPR-11
EN 55011
Class A
Group 2
Table 2: EMC Immunity
Generic standards, immunity standard for
industrial environments
EN 60947-4-3
ESD immunity
EN 61000-4-2
4 kV contact discharge
8 kV air discharge
RF interference immunity
10 V/m amplitude modulated
80 MHz-1 GHz
10 V/m amplitude modulated
1.4 GHz-2 GHz
Conducted disturbance immunity
10 V/m amplitude modulated
0.15 MHz-80 MHz
Burst immunity
EN 61000-4-4
2 kV power line
2 kV I/O signal line
Surge immunity
EN 61000-4-4/5
Power line-line 1 kV
Power line-earth 2 kV
Signal line-earth 2 kV
Signal line-line 1 kV
Magnetic fields immunity
Tests are not required.
Immunity is demonstrated by
the successful completion of
the operating capability test
Voltage dips, short interruptions and voltage
immunity tests
EN 61000-4-11
100%U, 70%U, 40%U,
Table 3: LVD Safety
Safety requirements for electrical equipment for
measurement, control and laboratory use
EN 61010-1
UL 508
ATTENTION
This product has been designed for class A equipment. Use of the product in domestic environments may cause
radio interference, in which case the user may be required to employ additional noise mitigation methods.
EMC filters are required in Phase Angle firing mode. The filter model and current level depend on the configura-
tion and load used. The power filter MUST be connected as close as possible to the CFW. You can use a filter
connected between the power line and CTF or an LC group connected between the CFW output and the load.
The CE declaration of conformity is available on request.