9
an adequate thermal exchange. Fit the device vertically
(maximum angle 10° to the vertical axis) see figure.
• Vertical distance between a device and the panel
wall >100mm
• Horizontal distance between a device and the panel
wall at last 10mm
• Vertical distance between a device and the next one
at last 300mm.
• Horizontal distance between a device and the next
one at last 10mm.
Check that the cable holder runners do not reduce
these distances, in this case fit the cantilever units op-
posite the panel so that the air can flow vertically with-
out any obstacles.
• dissipation of device thermal power with effects on
installation room temperature.
• thermal power dissipation with limits on installation
room temperature.
• requires exchange with external air or an air con-
ditioner to transfer dissipated power outside the
panel.
• maximum limits of voltage and derived power of
transients on the line, for which the solid state pow-
er unit contains protective devices (based on the
model).
• presence of dispersion current in CFW in noncon-
ducting state (current of a few mA due to RC Snub-
ber circuit to protect the thyristor).
Chromalox S.p.A. assumes no liability for any
damage to persons or property deriving from
tampering, from incorrect or improper use, or
from any use not conforming to the character-
istics of the controller and to the instructions
in this User Manual.
POWER SUPPLY
18...32Vdc
LEDs
OUTPUTS
CPU
INPUTS
POWER CONTROL
Main Processor
EEprom
RAM
OUT1,2,3
LOGIC
OUT5,6,7,8
CONTINUOUS
LOGIC
OUT5,6,7,8
TRIAC, RELAY
Connected to ±5V
CPU
Connected to
18...32Vdc
Connected to
5V (PORT 1)
Connected to
90...690V
Legend
1KV
1KV
2KV
1KV
DC / DC
±5V
1KV
DC / DC
5V
OUT1,2,3
LOGIC
4KV
max 690Vac
SSR
SSR1, SSR2, SSR3
max 230Vac
PORT 2
PORT 1
MODBus RS485
500V
1KV
FieldBus
Ethernet Modbus TCP
EtherCAT
CanOpen
DeviceNet
Profibus DP
ANALOG COMMAND INPUT
PID INPUT (IN1)
AUXILIARY INPUT
IN2, IN3, IN4, IN5
TA INPUT (I_load)
TA1, TA2, TA3
TV INPUT (I_line)
TV1, TV2, TV3
DIGITAL INPUT
DI1, DI2, DI3
1KV
MODBus RS485
FieldBus
EEthernet Modbus TCP
Ethernet IP
EtherCAT
CanOpen
Profibus DP
2KV
max 230Vac
OUT 9,10
RELÉ
Installation Diagram – 40 to 300A