MAINTENANCE

1

2

3

4

2-1/2 

REF.

HEATER ELEMENT CONDITION                                                              PROBABLE CAUSE

1. Water leakage at heater flange

2. Water leakage at heater element

to flange junction.

3. Burned wiring connections

4. Heater element has open circuit.

(Element looks OK but Ohmmeter
check shows infinite resistance).

5. Heater element has developed a

ground fault. When this occurs, a
hole may be formed in the sheath
material, allowing water to enter the
element.

1.

Heater bolts improperly tightened. Refer to flange tightening instructions.

2.

Debris on heater flange or generator flange surface. Clean prior to installation.

3.

Heater bolts not retorqued after initial operation. Refer to flange tightening 
instructions.

1.

Faulty weld or braze on element to flange connection or corrosion.

2.

Verify water is not exiting through heater terminal. Normally seen in condition #5.

1.

Loose wire connections. Tighten properly after inspection.

2.

High resistance in wire connection due to oxidation. Clean wires before 
reconnecting to element. Replace if necessary.

1.

Element has open circuit due to normal wear and tear to end life.

2.

If generator is undersized for its application, heaters will be over worked and
reach end of life sooner.

3.

Element has been overheated due to excessive scale build up. The scale acts as an
insulator retarding heat transfer to the water. Short life will result. If significant
scale is observed on element, this would indicate need for more frequent blowdown
or descaling.

4.

Wrong voltage supplied to element.

5.

Element not totally immersed in water. This causes a localized hot spot which
melts the wire inside the element. Cause of problem is fault in water level control
system. Elements damaged in this manner may be distorted. Repair and verify oper-
ation of the level control prior to restarting the heater.

1.

Corrosion of heater element sheath-use of corrosive descaler compounds will etch
sheath. Use only approved descaler to remove scale.

2.

Element has overheated due to excessive scale build up. This can cause localized
hot spot which sometimes arcs thru insulation and the ground metal sheath. More
frequent blowdown and/or descaling is needed.

3.

Element not totally immersed in water. This causes a localized hot spot which pro-
duces a hole in sheath. Cause of problem is fault in water level control system.
Elements damaged in this manner may be distorted.

4.

Excess vibration. Vibration could cause rubbing of elements wearing a hole in the
sheath. Vibration could be caused by large machinery nearby.

5.

Wrong voltage supplied to element.

IMMERSION HEATER FAILURE CAUSES

FIG. 3

Содержание CES-100

Страница 1: ...3 50 6 17 CES 135 13 9 136 30 5 410 8 50 4 50 8 17 1 30 CES 160 16 1 157 5 30 5 475 7 60 3 60 7 22 5 CES 180 18 4 180 30 5 543 8 60 4 60 8 22 5 Chromalox DIVISION 4 SECTION CES SALES REFERENCE DATE SE...

Страница 2: ...nection Conduit Box Element I Steam Outlet Sight Glass Element Access Door 5 8 7 16 Bolt Hole typical Drain Blowdown Valve K A B C Check Valve D H F E G Operating Pressure Control Safety Valve Outlet...

Страница 3: ...ust be main tained 3 Complete all piping to boiler Connect water line to tagged fitting on the motor and pump assembly if used or to tagged fitting on water control feeder 4 When any type of feed othe...

Страница 4: ...ed 6 WARNING Substitution of components or modifica tion of wiring system voids the warranty and may lead to dangerous operating conditions 7 SPECIAL INSTRUCTIONS FOR CUSTOMERS SUPPLY ING THEIR OWN CO...

Страница 5: ...R C2 FU4 FU5 FU6 2L1 2L3 2L2 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 3 2PS BR Heater Contactor Feed Water Boiler On 3 GND B FU6 B 1PB Off 1 GND 1 HTR C...

Страница 6: ...3 C2 FU7 FU8 FU9 C3 3L1 1L3 3L2 3 HTR C3 Heater Contactor Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 5 2PS BR Heater Contactors Feed Water Boiler On 3 GND...

Страница 7: ...C3 C4 FU 10 11 12 4 Htr FU10 FU11 FU12 C4 4L1 4L3 4L2 4 HTR C4 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 7 2PS BR Heater Contactor Feed Water Boiler On...

Страница 8: ...ND Cabinet Exterior Left Side Cabinet Exterior Right Side Panel Layout Feed Water Electrical Connection Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 9 FU 1...

Страница 9: ...H1 H4 H2 H3 FU24 FU23 FU22 FU21 FU20 FU13 C8 C7 7 HTR 6 HTR 7L1 8L3 8L2 8L1 5L3 7L2 C5 C7 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 11 FU 1 2 3 FU 4 5 6...

Страница 10: ...7L2 FU FU FU C7 C6 Heater Contactor Heater Contactor Heater Contactor Heater Contactor Heater Contactor Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 13 FU...

Страница 11: ...in valve or release man ual blowdown switch If low water cutout is automatic reset pump or solenoid will return water level to normal If low water cutout is manual reset then manual reset button on Mc...

Страница 12: ...ustomer Supplied 2 Turn on boiler and allow pressure to build up to operating pressure 3 Only open globe valve at quarter turns at first introducing smaller amounts of steam into process Avoid opening...

Страница 13: ...E CLOSED and the BOILER ON should light up again Now turn the wheel on the large timer until the OFF tab passes the TIME NOW arrow The BOILER ON light should go out and the valve should begin to open...

Страница 14: ...circuit balance is achieved The slightest change in the pressure of the controlled medium will cause a change in the number of elements energized to compensate for it thus keeping the pressure constan...

Страница 15: ...stage loads of the type used in Chromalox steam boilers It features progressive sequencing first on first off which equalizes the operating time of each load This control gives visual indication of e...

Страница 16: ...ed 3 Connect piping from discharge to water inlet check valve on boil er with minimum of 90 bends or other restrictions 4 All electrical wiring should be done by licensed electricians in accordance wi...

Страница 17: ...sure to drop to zero before ser vicing WARNING Provision should be made to prevent water damage from any eventual leaking of boiler or com ponents Install near a floor drain 2 On automatic feed units...

Страница 18: ...end life 2 If generator is undersized for its application heaters will be over worked and reach end of life sooner 3 Element has been overheated due to excessive scale build up The scale acts as an i...

Страница 19: ...50Hz 193 300175 002 Motor only used in ES 38020 115V 60Hz 193 300175 004 Strainer used in ES 38020 351 118664 001 V Band Mount used in ES 38002 ES 38020 355 300174 001 Solenoid Valve used in ES 38002...

Страница 20: ...0 amp 600V 128 121133 066 60 amp 600V 128 121133 067 Fuse Block 35 60 amp 60 amp 600V 129 047445 002 Power Terminal Blocks 3 pole 115 amp 1 line circuit 1 load circuits 303 071809 032 3 pole 175 amp 1...

Отзывы: