10
Menu
Code
Function
Adjustable Range
Factory
Default
Security
Level
ALSP
Alarm Set Point Temperature level that will
actuate the alarm.
0 to 100 °F or °C
5
B
ALdb
Alarm Dead Band Difference of temperature
from alarm set point before an active alarm
resets.
0 to 100 °F or °C
5
B
SPLL
Set Point Lower Limit Lower limit to which set
point may be set without security code access.
Sensor Range °F
or °C
Span Low
B
SPUL
Set Point Upper Limit Upper limit to which set
point may be set without security code access.
This prevents an operator from setting the set
point temperature to a level which would dam-
age equipment or process.
Sensor Range °F
or °C
Span High
B
outl
Output Limit Limits the percentage of output
that can be applied in proportional control.
0 to 100%
100
B
For calibration menus (CoFF, dFLt, & CALS), see Section 7–Calibration