MOUNTING REQUIREMENTS

Select a mounting location where there is
minimum vibration and the ambient temperature
range between 0 and 50 °C (32 and 122 °F).
The instrument can be mounted on a panel up to
15 mm thick with a square cutout of 45 x 45 mm.
For outline and cutout dimensions refer to page IV.
The surface texture of the panel must be better
than 6.3 

m

m.

The instrument is shipped with rubber panel
gasket.
To assure the IP65 and NEMA 4 protection, insert
the panel gasket between the instrument and the
panel as show in fig. 1.
While holding the instrument against the panel
proceed as follows:
1) insert the gasket in the instrument case;
2) insert the instrument in the panel cutout;
3) pushing the instrument against the panel, insert

the mounting bracket;

4) with a screwdriver, turn the screws with a

torque between 2.7 to 3.5 in-lb (0.3 and 0.4
Nm).

Fig. 1

Panel

bracket

Screw

Gasket

1601-1-0C.p65

5/2/00, 1:45 PM

1

Содержание 1601

Страница 1: ...1601 Temperature Controller Issue date r USER S MANUAL March 2000 0037 75236 1601 0 0C p65 5 2 00 1 45 PM 1 ...

Страница 2: ...RS 6 OPERATOR MODE 10 Indicators 10 Pushbutton function 11 Manual reset of the alarms 11 SMART algorithm 11 Output power OFF 12 Direct access to the set point 12 Display of the set point value 12 Bargraph operating 13 Lamp test 13 OPERATOR PARAMETERS 13 ERROR MESSAGES 15 GENERAL INFORMATIONS 17 MAINTENANCE 18 DEFAULT PARAMETERS A 1 II 1601 0 0C p65 5 2 00 1 45 PM 2 ...

Страница 3: ...1 Relay 3 Amps at 250 Vac Resistive 6 SSR Drive 14 Vdc at 20 mA Code Output 2 Alarm 1 Relay 1 Amp at 250 Vac Resistive load Code 0 Add to complete model number Code Instrument Power 3 100 240 Vac 5 24 Vac dc Code 0 Add to complete model number 1601 6 1 0 3 0 Typical Model Number 1601 0 0C p65 5 2 00 1 45 PM 3 ...

Страница 4: ...OUTLINE AND CUT OUT DIMENSIONS V 1601 0 0C p65 5 2 00 1 45 PM 4 ...

Страница 5: ...VI 1601 0 0C p65 5 2 00 1 45 PM 5 ...

Страница 6: ... mm The instrument is shipped with rubber panel gasket To assure the IP65 and NEMA 4 protection insert the panel gasket between the instrument and the panel as show in fig 1 While holding the instrument against the panel proceed as follows 1 insert the gasket in the instrument case 2 insert the instrument in the panel cutout 3 pushing the instrument against the panel insert the mounting bracket 4 ...

Страница 7: ...HERMOCOUPLE INPUT WIRING NOTE 1 Don t run input wires together with power cables 2 For TC wiring use proper compensating cable for example J TC extension wire for J TC preferable shielded 3 when a shielded cable is used it should be connected at one point only Shield Shield 3 2 _ 3 2 _ CONNECTION DIAGRAMS Connections are to be made with the instrument housing installed in its proper location Fig 2...

Страница 8: ...e protected by varistor against inductive load with inductive component up to 0 5 A The contact rating of the OUT 1 is 3A 250V AC on resistive load The contact rating of the OUT 2 is 1A 250V AC on resistive load The number of operations is 1 x 105 at specified rating NOTES 1 Toavoid electricshock connectpower line at the end of the wiring procedure 2 ForpowerconnectionsuseNo16AWG or larger wires r...

Страница 9: ...or assures a correct protection up to 0 5 A of inductive component but the OUT 1 NC contact is not protected The same problem may occur when a switch is used in series with the internal contacts as shown in Fig 7 Fig 7 EXTERNAL SWITCH IN SERIES WITH THE INTERNAL CONTACT In this cases it is recommended to install an additional RC network across the external contact as show in Fig 7 Chromalox snubbe...

Страница 10: ...that line voltage corresponds to the description on the identification label 2 Toavoid electricshock connectpowerlineat the end of the wiring procedure 3 For supply connections use No 16 AWG or larger wires rated for at last 75 C 167 F 4 Use copper conductors only 5 Don t run input wires together with power cables 6 For 24 V AC DC the polarity is not important 7 The power supply input has NO fuse ...

Страница 11: ...input span NOTES 1 the minimum input span P3 P2 is 300 C or 600 F for TC input and 100 C or 200 F for RTD input 2 Changing P2 and or P3 parameters the rL and rH parameters will be realligned to it 3 If during configuration procedure a C range has been selected it is necessary to put the C label on the front of the instrument covering the F indication The sticker is located with the gasket in the s...

Страница 12: ...long the whole range When P1 5 P9 is programmable from 19 9 to 19 9 C When P1 5 P9 is programmable from 199 to 199 C or F P4 Main output action r reverse action heating d direct action cooling P5 Output 2 functions 0 Not provided 1 Process alarm 2 Band alarm 3 Deviation alarm 4 instrument failure indicator under or over range CJC or A D converter failure P6 Output 2 operator mode P6 is available o...

Страница 13: ...f the parameters can be modified except the SP To Unlock the device insert the security code 500to999 whenselectingasecuritycodebetween these two numbers the operation is identical to a selection from 2 to 499 except that both the set point and the alarm set point can be modi fied P12 Control output maximum rate of rise Programmable from 1 to 10 of the output per second The ramp is applied when th...

Страница 14: ...ter may be programmed from P17or P18 value to 99 9 P17 Minimum value of the proportional band settable by the SMART function in heating control only It may be programmed from 1 0 to P16 value P18 Not Available P19 Not Available P20 Minimum value of integral time settable by SMART function P20 is programmable from 00 1 10 seconds to 02 0 2 minutes P21 Extension of the anti reset wind up Range from ...

Страница 15: ...red parameter by the FUNC pushbutton then set the new value by s or t pushbuttons Press FUNC pushbutton to store the new value and step to the next parameter NOTE 1 If during parameter modification no pushbutton is pressed for more than 10 seconds the instrument reverts automatically to the normal display mode and the new setting of the last parameter will be lost 2 The instrument doesn t display ...

Страница 16: ...g the s and t pushbuttons select ON and push the FUNC pushbutton again The alarm cannot be reset until the alarm condition has disappeared SMART ALGORITHM The SMART feature automatically sets the best control action To enable the SMART function push the SMART pushbutton for more than 1 5 s when the instrument is in normal display mode The SMART LED will light continuously or flash according to the...

Страница 17: ...thout affecting the process With the output off the 1601 can be used as an indicator To turn OFF the output signal hold the s pushbutton first and then push FUNC pushbutton After maintaining pressure on both of them for more than 3 seconds the instrument will show OFF instead of the set point value Since the 1601 has only one display it is possible to toggle from OFF to measured value by depressin...

Страница 18: ... or the desired status By pushing the FUNC pushbutton the instrument saves the new value or the new status and goes to the next parameter Param DESCRIPTION SP Set point in eng units Range from rL to rH n rS Manual reset of the alarms This parameter is available only when a latching alarm has been programmed Set ON and push the FUNC pusbutton to reset the alarms nnn Security code for parameter prot...

Страница 19: ...ion Range from 1 s to 9 min and 59 s if 0 is set the derivative action is excluded IP Integral pre load This parameter is skipped when PB 0 Range from 0 to 100 for one control output C Output 1 heating cycle time in seconds This parameter is present if PB parameter is different from 0 only Range From 1 to 200 s rL Set point low limit in eng units Range from min range value P2 to rH Note When P2 ha...

Страница 20: ... input resistance is less than 15 ohm Short circuit sensor detection NOTE When The instrument is set for one output only and an OVERRANGE is detected the OUT 1 turns OFF if reverse action or ON if direct action The instrument is set for one output only and an UNDERRANGE is detected the OUT 1 turns ON if reverse action or OFF if direct action NOTE when an overrange or an underrange is detected the ...

Страница 21: ... hardware error on the CPU card 200 Protect register memory error The controller performs this check every 2 seconds Set the switch V2 in open condition Switch on the controller Set the switch V2 in closed condition and power the controller 201 219 Configuration parameter error 2xx where xx is the Configuration code The two less significant digit s show the number of the wrong configura tion param...

Страница 22: ... R4 R5 R11 Q2 R3 PZ2 PZ1 C15 K2 C9 V2 WORNING Do not attempt calibration without the recommended simulator or calibrator For this calibration procedure it is necessary to use calibrators with the following accuracy and resolution ACCURACY 1 For TC input 0 005 output 0 001 range 5 mV 2 For RTD input 0 02 0 0025 W decade 3 For cold junction compensation better than 0 1 C RESOLUTION 1 For TC input 1 ...

Страница 23: ...between calibrator and controller under test as shown in fig 12 2 The display will show tL F where F means OFF 2 Set calibrator to 0 000 mV 3 Push or pushbutton the display will change to tL n where n means On 4 After 30 seconds start calibration by pushing the FUNC pushbutton Only the decimal point of the last significant digit will light to indicate that the controller is performing the calibrat...

Страница 24: ...hbutton the instrument will go to the next calibration group COLD JUNCTION CALIBRATION NOTE make sure that tL and tH parameters are correctly calibrated before rJ parameter calibration rJ ACTUAL VALUE The display will show rJ F where F means OFF 1 Measure the temperature close to terminals 2 and 3 using an instrument with accuracy better than 0 1 C see Fig 13 Fig 13 2 Wait for a few minutes to all...

Страница 25: ...rt the calibration by pushing the FUNC pushbutton Only the decimal point of the last significant digit will light to indicate that the controller is performing the calibration routine At the end of this calibration routine the controller will go to the next parameter PH RTD INPUT FULL SCALE VALUE The display will show PH F where F means OFF 1 Set the resistor box to 300 00 W 3 Push or pushbutton t...

Страница 26: ...e P 10 and 153 10 counts 3 Set 200 00 W on the the resistor box The result should be P 20 and 151 10 counts 4 Push the FUNC pushbutton The calibration procedure is complete and the display will show CAL When it is desired to go to the configuration procedure depress the pushbutton and the display will show CnF and the controller is in configuration mode If the previous configuration is correct swi...

Страница 27: ...ity and safety requirements This instrument is marked CE Therefore it is conforming to council directives 89 336 EEC reference harmonized standard EN 50081 2 and EN 50082 2 and to council directives 73 23 EEC and 93 68 EEC reference harmonized standard EN 61010 1 Installation category II Temperature drift 200 ppm C RJ excluded 400ppm CforRTDinputwith 19 9 99 9 Crange and TC type T Reference juncti...

Страница 28: ...n the SMART function is enabled CONTROL OUTPUTS OUTPUT 1 heating a Relay output with SPDT contact contact rating 3A 250 V ac on resistive load b Logic voltage for SSR drive Logic status 1 24 V 20 1 mA 14 V 20 20 mA Logic status 0 0 5 V Output action direct reverse programmable OUTPUT 2 alarm 1 a Relay output with SPST contact contact rating 1A 250 V ac on resistive load By internal jumper it is po...

Страница 29: ...he display will show g Press FUNC pushbutton the display will show This means that the loading procedure has been initiated After about 3 seconds the loading procedure is terminated and the instrument reverts to NORMAL DISPLAY mode The following is a list of the default operative parameters loaded during the above procedure PARAMETER DEFAULT VALUE SP minimum range value nnn OFF AL minimumrange val...

Страница 30: ... e Press s pushbutton to select between table 1 european or table 2 american default parameter set The display will show f Press FUNC pushbutton the display will show This means that the loading procedure has been initiated After about 3 seconds the loading procedure is terminated and the instrument reverts to the CnF parameter The following is a list of the default parameters loaded during the ab...

Страница 31: ...ncluding but not limited to attorney s fees and indemnifies Chromalox against any liability to Chromalox s vendors arising out of such litigation Upon buyer s submission of a claim as provided above and in its substantiation Chromalox shall at its option either i repair or replace its Products parts or work at the original f o b point of delivery or ii refund an equitable portion of the purchase p...

Страница 32: ...AKER BOULEVARD LAVERGNE TN 37086 3536 PHONE 615 793 3900 FAX 615 793 3563 WIEGAND INDUSTRIAL DIVISION WIEGAND INDUSTRIAL DIVISION WIEGAND INDUSTRIAL DIVISION WIEGAND INDUSTRIAL DIVISION WIEGAND INDUSTRIAL DIVISION EMERSON ELECTRIC CO 1601 A 0C p65 5 2 00 3 37 PM 4 ...

Отзывы: