P14 -Display of the operator parameters.
This parameter is available only if P11 is different
from 0.
This parameter allows you to enable/disable the
display of the protected parameters during
"operator mode".
OFF = protected parameters cannot be displayed
ON = protected parameters can be displayed
P15 - SMART function enabling/ disabling
0 = The SMART function is disabled
1 = The SMART function enabling/disabling is
NOT protected by the security code (P11).
2 = The SMART function enabling/disabling is
protected by the security code (P11).
P16 - Maximum value of the proportional band
settable by the SMART function
This parameter may be programmed from P17or
P18 value to 99.9.
P17 - Minimum value of the proportional band
settable by the SMART function in heating
control only.
It may be programmed from 1.0% to P16 value.
P18 - Not Available
P19 - Not Available
P20 - Minimum value of integral time settable
by SMART function.
P20 is programmable from 00.1 (10 seconds) to
02.0 (2 minutes).
P21 = Extension of the anti-reset-wind up
Range: from -30 to +30 % of the proportional
band.
NOTE
: a positive value encreases the high limit of
the anti-reset-wind up (over set point) while a
negative value decreases the low limit of the anti-
reset-wind up (under set point).
The advanced configuration procedure is
completed and the instrument shows " CnF" on
the display.
Pressing the "FUNC" will return the unit to the first
configuration parameter.