P10 = Threshold of the “Soft Start” function.
Enter the threshold value, in °C or °F, for the auto-
matic start of the "Soft Start" function (limiting output
power). If the unit powers up below the threshold
value, the "Soft Start" function is enabled and limits
the power output to "OLH" for "tOL" minutes. "OLH"
and "tOL" are set in operator mode.
P11 = User defined security code
0 = device unlocked. All the parameters can be
modified
1 = device locked. None of the parameters can be
modified except the SP.
2 to 499 = Select the security code.
During the
“operator mode”,
the “software key”
parameter will show one of the following
figures:
A)
The device is “Unlocked”
and all parameters can be
modified.
To make the device
“Locked” insert a number
different from the “security
code”. Now none of the
parameters can be modified
except the SP.
B)
The device is “locked” and
none of the parameters can
be modified except the SP.
To “Unlock” the device,
insert the “security code”.
500 to 999 = when selecting a security code between
these two numbers, the operation is identical to
a selection from "2 to 499" except that both the
set point and the alarm set point can be modi-
fied.
P12 = Control output maximum rate of rise
Programmable from 1 % to 10 % of the output per
second.
The ramp is applied when the controller changes
the percent of output desired. Above a 10 % the
display will show "InF" meaning that no ramp is
imposed and the output immediatelychanges to
the PID calculated value.
P12 not used if ON/OFF control selected.
P13 = Not used
ADVANCED CONFIGURATION
The configuration procedure is completed and the
instrument shows "
-.-.-.
" on both displays.
When it is desired to end the configuration
procedure push the FUNC pushbutton; the display
will show "CnF".
When it is desired to access to the advanced
configuration parameter procede as follows:
1) using
s
and
t
pushbutton set to 219.
2) push the FUNC pushbutton.