Three kinds of alarm output points (12 points, 24 points, and 36 points) are prepared. Confirm the model code.
For the alarms and setting and connections of alarm outputs, refer to [
Ⅰ.
Instruction Manual]
.
1. Alarms and alarm output setting ------- 8-6 Alarm setting
Setting and assignment of alarm output channels are as shown below. Be careful since any setting other than
specified in the following table cannot be done.
No. of output points Channel No. Output relay No. setting
12
points
1
to
12
801
to
812
24
points
1
to
24
801
to
824
36
points
1
to
36
801
to
836
2. Connections ------- 4-3 Connections of each section 4-3-4 Alarm output terminals
3. Failure output setting
A failure output can be sent to alarm output terminals. For the setting method, observe the following procedure.
【
Setting method
】
①
Press Menu key to enter the setting display mode.
A window opens and a setting items table is displayed.
②
Select a desired item to be set by moving the cursor by means of
・
・▲・▼
keys.
③
Select FAIL OUT.
④
Press Enter key to enter the parameter entry mode of the desired item
to be set. A window opens and a setting parameter entry screen is
displayed.
(For the setting parameter entry screen, refer to
⑥
)
⑤
For stopping the setting, press Esc key. The screen returns to the last
one, each time Esc key is pressed once.
⑥
Move the cursor to a desired item to be set by
・
・▲・▼
keys.
Each time Enter key is pressed once, the cursor moves in the
sequence of Relay No.
→
Set. Input a setting parameter to the
parameter input area at the output destination by pressing numeric
keys. Setting is as shown below.
Any setting other than described below cannot be done
.
No. of output points
Settable output relay No.
12 points
801
-
812
24 points
801
-
824
36 points
801
-
836
When the communication interface is attached, output relay No. 800
can be designated in addition to the above numbers.
After setting this screen, bring the cursor to Set .
⑦
Terminate the setting (change, addition) by pressing Enter key.
(
Note1
)
Failure output destination is set to [800] at the delivery time from our
factory.
When the communication interface is specified to be provided, a failure
output signal is sent to output relay No. 800. However, when the
communication interface is specified to be not provided, but the alarm
output is specified to
be sent, a channel must be set out of 801
-
836,
referring to the above table.
Example
For outputting to alarm output terminal channel 1,
set output relay No. to [801]
Set by using
・
・
▲・▼
keys and numeric
keys (Change, addition)
Start
Menu key
Set?
①
Esc key
NO
⑤
End
YES
⑥
Selection of setting items
・
・▲・▼
keys
②
Enter key
③
Setting parameter display
Enter key
Setting ends
⑦
FAIL OUT
④