[DB600] General Instruction Manual
MODE 2
- 78 -
5-4-3
Program pattern setting
Up to four patterns can be set, allowing you to select a desired pattern during operation.
Example of program pattern setting
1.
Pattern
No.
1
Step No. 00
01
02
03
04
05
06
07
08
09
10
11
12
13
Number of
steps
12
PV start SV
SV [°C]
0
100 100 150 150 200 200 250 250 300 300 200 200
Time [H:M]
1:00 2:00 0:30 0:30 0:30 0:30 0:30 0:30 0:30 1:00 0:00 3:30
Execution
No.
No.1 No.0 No.2 No.0 No.0 No.3 No.0 No.0 No.0 No.4 No.0 No.8
END
output
0.0
Pattern
link
OFF
- Setting procedure -
(1)
Press and hold the
key on the operation screen to display the MODE0 initial setting
screen.
(2)
Press the
keys to display the MODE2 initial screen and then press the
key.
(3)
On the pattern setting screen, select the pattern No. "1" and step No. "00" by pressing the
keys, and then press the
key.
(4)
Set the start step. On the number of steps screen, set "12" using the
and
keys
and then press the
key to register it. Press the
key again to go to the next screen.
(5)
On the program operation PV start screen, set "SV" using the
keys and then press
the
key to register it. Press the
key again to go to the next screen.
(6)
On the start SV screen, set "0" using the
and
keys and then press the
key to register it. Press the
key again to go to the next screen.
(7)
Set the step No. 01. Press the
key. On the SV for program operation screen, set "100"
using the
and
keys and then press the
key to register it. Press the
key again to go to the next screen.
(8)
On the step time screen, set "1:00" using the
and
keys and then press the
key to register it. Press the
key again to go to the next screen.
(9)
On the execution No. selection for program operation screen, set "No. 1" using the
keys and then press the
key to register it. Press the
key again to go to the next
screen.
(10)
Set the step No. 02 to step No. 12 in the same manner.
(11)
Set the end step. Press the
key. On the output 1 at END screen, set "0.0" and press the
key to register it. Press the
key again to go to the next screen.
* For the specification with 2 outputs, the output 2 at END screen will be displayed.
(12)
On the linked pattern No. screen, set "OFF" using the
keys and then press the
key to register it.
0
100
200
300
400
0
60 120 180 240 300 360 420 480 540 600 660
S
V
[
℃
]
パターン経過時間
[
分
]
Pattern elapsed time [min]