Figure 14: Overview of sewerage with condensation water pump
1. Drain trap
2. Unit
3. Condensation water hose
4. Drain connection (must be accessible through a maintenance hatch)
5. Maintenance hatch (min. 600 mm)
6. Condensation sewerage
7. Supplementary air
Before you install the sewerage, make sure that
•
the cross-sectional area of the condensation water network is sufficient.
•
the cross-sectional area of the condensation water pipe is sufficient, at least
22 mm.
•
you install a drain trap to the condensation water pipeline, if condensation
water is directed to the sewerage system of the property. The drain trap is
dimensioned according to the installation height to ensure that water is
constantly discharged at a sufficient rate.
•
the condensation water pipe is insulated, if the unit is installed in rooms
where condensation can occur on the pipe surface.
•
you support the condensation water pipe so that it does not bend at any
place.
•
you take into account the availability of supplementary air, when planning the
sewerage.
When you install the sewerage, make sure that
•
you connect the condensation pump hose to the sewerage from the upper
side.