background image

CMS440P2

Installation Instructions

6

Isolated Ground Receptacle

This product incorporates an isolated ground receptacle,
identified by the orange triangle on its face. This feature may be
useful to reduce common noise in the connected equipment. Its
intended use is to reduce electrical noise (electromagnetic
interference) by purposely insulating the grounding circuit from
any metallic wiring system. The ground pin of the receptacle is
connected to the green/yellow wire and is isolated from the
metal mounting yoke of the receptacle. The accessible metal of
the product is connected to the green wire. If it is not desired to
use this feature, connect the green/yellow and green wires
together.

References

Application Guide for Isolated Ground Wiring Devices 2007.
National Electrical Manufacturers Association (NEMA)

IEEE Std 1100

-2005, “IEEE Recommended Practice for

Powering and Grounding Electronic Equipment” (Emerald
Book), Section 8.5.3.2.

IEEE Std 142™-2007, “IEEE Recommended Practice for
Grounding of Industrial and Commercial Power Systems”
(Green Book), Sections 5.5.1, 5.5.2

NFPA-70, “National Electrical Code”, Article 250.146
Connecting Receptacle Grounding Terminal to Box.

(D) Isolated Ground Receptacles. Where installed
for the reduction of electrical noise (electromagnetic
interference) on the grounding circuit, a receptacle
in which the grounding terminal is purposefully
insulated from the receptacle mounting means shall
be permitted. The receptacle grounding terminal
shall be connected to an insulated equipment
grounding conductor run with the circuit conductors.
This equipment grounding conductor shall be
permitted to pass through one or more panel boards
without a connection to the panel board grounding
terminal bar as permitted in 408.40, Exception, so
as to terminate within the same building or structure
directly at an equipment grounding conductor
terminal of the applicable derived system or service.
Where installed in accordance with the provisions of
this section, this equipment grounding conductor
shall also be permitted to pass through boxes, wire
ways, or other enclosures without being connected
to such enclosures.

Informational Note: Use of an isolated equipment
grounding conductor does not relieve the
requirement for grounding the raceway system and
outlet box.

C22.2 No. 1, “Canadian Electrical Code, Part 1”, Rule 10-906
Bonding conductor connection to circuits and equipment.

(6) A bonding jumper shall be installed to connect
the bonding conductor to the grounding terminal of
a receptacle and in such a manner that
disconnection or removal of the receptacle will not
interfere with, or interrupt grounding continuity.

(7) In the case of metallically enclosed systems
where the grounding path is provided by the metal
enclosure, a bonding jumper shall be installed to
bond the grounding terminal of the receptacle to the
enclosure.

(8) Notwithstanding Sub-rules (6) and (7), the
bonding jumper, in the case of receptacles having
grounding terminals isolated from the mounting
strap required for special equipment, shall be

permitted to be extended directly back to the
distribution panel.

WARNING:

IMPROPER INSTALLATION CAN RESULT IN

DEATH OR SERIOUS PERSONAL INJURY! This accessory
should be installed by qualified personnel.

IMPORTANT ! :

In addition to the CMS440 installation

instructions accompanying the products, the following steps
must also be taken when installing the

CMS440P2

.

NOTE:

The CMS440P2 must be connected to a 15 Amp

branch circuit.

Installation to Ceiling

1.

Remove 6-32 x 1/2" Phillips flat head screw and #06 locking
washer from outlet box. (See Figure 1)

Figure 1

2.

Remove one Phillips head screw holding outlet box to outer
housing at the straight slot and loosen the other screw. (See
Figure 2)

Figure 2

3.

Rotate outlet box counter-clockwise until it is free to be
removed from housing. (See Figure 2)

4.

Remove outlet box from housing. (See Figure 2)

x 1

1

locking washer

2

x 2

3

4

outlet box

(view from below)

straight slot

Содержание CMS440P2

Страница 1: ...C T I O N S A D D E N D U M Above Tile and Ceiling Tile Kits Spanish Product Description German Product Description Portuguese Product Description Italian Product Description Dutch Product Description...

Страница 2: ...ute cables as shown in these installation instructions To disconnect turn off power at source WARNING RISK OF ELECTRIC SHOCK Make sure the outlet is properly grounded See Grounding Instructions WARNIN...

Страница 3: ...el Chave de bocas Chiave a punte aperte Steeksleutel Cl fourche By Hand A mano Von Hand Com a m o A mano Met de hand la main Hex Head Wrench Llave de cabeza hexagonal Sechskantschl ssel Chave de cabe...

Страница 4: ...CMS440P2 Installation Instructions 4 DIMENSIONS CMS440P2 DIMENSIONS INCHES MILLIMETERS...

Страница 5: ...Instructions CMS440P2 5 TOOLS REQUIRED FOR INSTALLATION ADDITIONAL PARTS A 1 CMS440P2 10 32 x 3 8 Grounding wire Earthing symbol IEC 60417 No 5019 affixed adjacent to grounding terminal B 1 C 1 D 1 O...

Страница 6: ...l of the applicable derived system or service Where installed in accordance with the provisions of this section this equipment grounding conductor shall also be permitted to pass through boxes wire wa...

Страница 7: ...avoid unnecessary bends NOTE An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors except that it is...

Страница 8: ...ing removed 06 32 x 1 2 Phillips flat head screw and 06 lock washer See Figure 6 NOTE Be sure to line up hole in outlet cover over light in outlet Figure 6 Outlet Box Use NOTE The PROTECTED light indi...

Страница 9: ...Installation Instructions CMS440P2 9...

Страница 10: ...CMS440P2 Installation Instructions 10...

Страница 11: ...Installation Instructions CMS440P2 11...

Страница 12: ...com 05 16 USA International A 6436 City West Parkway Eden Prairie MN 55344 P 800 582 6480 952 225 6000 F 877 894 6918 952 894 6918 Europe A Franklinstraat 14 6003 DK Weert Netherlands P 31 0 495 580...

Отзывы: