Technical specifications for CPG 120 John Deere
Readings on gauges
Settings of switches
Specifications of the engine/alternator/unit
Gauge
Reading
Unit
Ammeter L1-3 (P1-3)
Below max. rating
A
Voltmeter (P4)
Depends upon selector switch
V
Switch
Function
Activates at (US)
Activates at (Metric)
Engine oil pressure
Shut down
7.25 psi
0.5 bar
Engine coolant temperature
Shut down
217.40°F
103°C
US
Metric
Reference conditions 1)
Rated frequency
60 Hz
60 Hz
Rated speed
1800 rpm
1800 rpm
Generator service duty
PRP
PRP
Absolute inlet pressure
100 kPa
100 kPa
Relative air humidity
30%
30%
Air inlet temperature
77°F
25°C
Limitations 2)
Maximum ambient temperature
122°F
50°C
Altitude capability
13,000 ft
4000 m
Relative air humidity maximum
85%
85%
Minimum starting temperature unaided
0 °F
-
2
°C
Minimum starting temperature aided
-13°F
-25°C
Performance data 2) 3) 5)
Rated active power (PRP) 3 php
95 kW
95 kW
Rated active power (PRP) 1ph
72 kW
72 kW
Rated power factor (lagging) 3phase
0,80
0,80
Rated power factor (lagging) 1phase
1.0
1.0
Содержание CPG 90-120 JD
Страница 1: ...CPG 90 120 JD Instruction Manual for AC Generators English ...
Страница 2: ......
Страница 19: ... 19 This is the described menu flow for changing the unit type ...
Страница 47: ... 47 Circuit diagrams ...
Страница 48: ... 48 1310 3200 01 00 Applicable for CPG 90 120 John Deere Power circuit ...
Страница 49: ... 49 ...
Страница 51: ... 51 ...
Страница 52: ... 52 1310 3200 00 00 Applicable for CPG 90 120 John Deere Engine circuit Qc1002TM ...
Страница 53: ... 53 ...
Страница 55: ... 55 ...
Страница 56: ...Printed in Belgium 04 2010 1310 3012 23 www cp com ...