- 24 -
Spillage free skid
A spillage free skid with forklift slots allows the
customer to transport the generator easily with a
forklift.
It avoids accidental spilling of engine fluids.
Engine coolant heater
To make sure that the engine can start and accept load
immediately, an external cooling water heater
(2000 W, 240 V) is provided which keeps the engine
temperature between 38°C (100°F) and 49°C
(120°F).
Operating instructions
Installation
–
Place the generator on a horizontal, even and solid
floor. The generator can operate in a slant position
not exceeding 15° (in both senses: front/rear and
left/right).
–
The generator should be kept with the doors
closed, in order to avoid the ingress of water and
dust. Dust ingress reduces the lifetime of filters
and may reduce your generator's performance.
–
Check that the engine exhaust is not directed
towards people. If the generator is operated
indoors, install an exhaust pipe of sufficient
diameter to duct the engine exhaust towards the
outside. Check for sufficient ventilation so that the
cooling air is not recirculated. If necessary,
consult Chicago Pneumatic.
–
Leave enough space for operation, inspection and
maintenance (at least 1 meter at each side).
–
Check that the inner earthing system is in
compliance with the local legislation.
–
Use coolant for the engine cooling system. Refer
to the Engine instruction book for the proper
coolant mixture.
–
Check the tightness of the bolts and nuts.
–
Install the earthing rod as near as possible to the
generator and measure its diffusion resistance
(max. 1 k
Ω
) in order not to have a contact voltage
higher than 25 V at 30 mA leakage current.
–
Check that the cable end of the earthing rod is
connected to the earth terminal.
Connecting the generator
Precautions for non-linear and
sensitive loads
The most common non-linear, 3-phase loads are
thyristor/rectifier-controlled loads, such as convertors
supplying voltage to variable speed motors,
uninterruptable power supplies and Telecom
supplies. Gas-discharge lighting arranged in single-
phase circuits generate high 3rd harmonics and risk
for excessive neutral current.
In your own interest, always strictly
observe all relevant safety
instructions.
Do not operate the generator in excess
of the limitations mentioned in the
Technical Specifications.
Local rules concerning the setting up
of low voltage power installations
(below 1000 V) must be respected
when connecting site distribution
panels, switch gear or loads to the
generator.
For information about indoor
installation, consult your local
Chicago Pneumatic dealer.
Non-linear loads draw currents with
high contents in harmonics, causing
distortion in the wave form of the
voltage generated by the alternator.
Содержание CPG 90-120 JD
Страница 1: ...CPG 90 120 JD Instruction Manual for AC Generators English ...
Страница 2: ......
Страница 19: ... 19 This is the described menu flow for changing the unit type ...
Страница 47: ... 47 Circuit diagrams ...
Страница 48: ... 48 1310 3200 01 00 Applicable for CPG 90 120 John Deere Power circuit ...
Страница 49: ... 49 ...
Страница 51: ... 51 ...
Страница 52: ... 52 1310 3200 00 00 Applicable for CPG 90 120 John Deere Engine circuit Qc1002TM ...
Страница 53: ... 53 ...
Страница 55: ... 55 ...
Страница 56: ...Printed in Belgium 04 2010 1310 3012 23 www cp com ...