2. PRODUCT FEATURES
2.1. DESCRIPTION
PEL: P
ower &
E
nergy
L
ogger
The PEL102, PEL103 and PEL are simple-to-use single-, dual-, and three-phase (Y,
∆
) Power & Energy Loggers.
The PEL offers all necessary functions for Power/Energy data logging for most 50 Hz, 60 Hz, 400 Hz and DC distribution systems
worldwide, with many connection possibilities. The PEL is designed to work in 1000 V CAT III and 600 V CAT IV environments.
The PEL is compact and can be incorporated in many distribution panels.
The PEL provides the following measurements and calculations:
Direct measurements of voltages up to 1000 V CAT III and 600 V CAT IV
Direct measurements of current from 50 mA up to 10 000 A with MA194 external current sensors
Power measurements: active (W), reactive (var) and apparent (VA)
Energy measurements: active (source and load (Wh)), reactive 4 quadrants (varh) and apparent (VAh)
Power Factor (PF), cos
ϕ
, and tan
Φ
Crest Factor
Total Harmonic Distortion (THD) for voltages and currents
Harmonics from the fundamental signal up to the 50th order for 50/60 Hz voltages and currents
Frequency measurements
RMS and DC measurements @ 128 samples/cycle – all phases simultaneously
Bright white triple LCD display with white backlighting for the PEL 103 and PEL 104 (3 phases shown simultaneously)
Storage of measured and calculated values on an SD-Card or SDHC-Card
Automatic recognition of the different types of current sensors
Configuration of current and voltage ratios with external sensors
Supports 17 types of connections or electrical distribution systems
USB, LAN, and Bluetooth communication
PEL Transfer software for data recovery, configuration and real-time communication with a PC
Android application to communicate in real time and configure the PEL from a smartphone or a tablet.
For PEL 104 only:
Wi-Fi and 3G-UMTS/GPRS communication.
Communication with up to four data loggers - L452 Data Loggers (optional), to record voltages, currents, and events).
Measurements of the fundamental active power.
32 programmable alarms on the measurements or on the analog inputs with the L452 Data Logger (optional), which communicates
via Bluetooth.
IRD server to communicate using private IP addresses.
Sending of periodic reports by email.
Содержание pel 102
Страница 1: ...Power energy logger EN User s manual PEL 102 PEL 103 PEL 104 ...
Страница 24: ...24 Aggregation period Date and time IP address scrolling Wi Fi address scrolling PEL104 ...
Страница 34: ...34 Two phase 3 wire 2P 3W V1 V2 U12 VN P Q S PF P Q S tan ϕ ϕ V2 V1 ϕ I1 V1 ϕ I2 V2 I1 I2 f ϕ I2 I1 ...
Страница 36: ...36 Three phase 3 wire balanced 3P 3W b U12 U23 U31 f P Q S PF P Q S tan ϕ I1 I2 I3 ϕ I1 U12 ...
Страница 38: ...38 Three phase 4 wire wye balanced 3P 4WYb I1 I2 I3 V1 V2 V3 VN U12 U23 U31 f P Q S tan ϕ ...
Страница 39: ...39 DC 2 wire dC 2W DC 3 wire dC 3W P Q S PF ϕ I1 V1 P Q S tan ϕ P I V VN I1 I2 IN ...
Страница 40: ...40 DC 4 wire dC 4W P I1 I2 I3 IN V1 V2 V3 VN V1 V2 VN ...
Страница 48: ...48 Two phase 3 wire 1P 3W I1 I2 V1 V2 U12 VN P Q S P Q S ...
Страница 49: ...49 Three phase 3 wire 3P 3W 2 3P 3W 3 3P 3WO2 3P 3WO3 3P 3WY2 3P 3WY3 3P 3W b I1 I2 I3 U12 U23 U31 P Q S P Q S ...
Страница 51: ...51 P Q S ...
Страница 85: ...85 ...