27
1.3. THREE-PHASE MINIFLEX
®
The MiniFlex
®
series MA130 sensor converts alternating currents ranging from 30 to 3000 A into
proportional AC voltages. It comprises 3 sensors 25 cm long connected to the electronic unit. The output
is via 3 BNC connectors on which it is possible to place the adapters provided in order to obtain outputs
with 2 safety plugs.
The three outputs of the electronic unit can be connected to a standard wattmeter (as auxiliary inputs),
to multimeters, to a recorder, etc.
OFF
30 A
300 A
3000 A
30 A : 100 mV / A
300 A : 10 mV / A
3000 A : 1 mV / A
AC CURRENT PROBE
MA 130
On
Auto Power Off
OL
L1
L2
L3
L1 L3
L2
600 V CAT III
L1
L2
L3
L1
L2
L3
P
3 current sensors for 3
phases.
3 BNC
connectors, each
corresponding to
a sensor.
The multimeter or instrument connected must have a maximum voltage and a measurement
category at least equal to those of the MiniFlex
®
sensor, since otherwise the maximum voltage
and category of the assembly will be those of the lowest‑rated component.
3 BNC / safety
plugs (19 mm
centres)
adapters.