Chatsworth Products RIM-750 Скачать руководство пользователя страница 1

1-Wire Sensor Connections

Plug in your temperature (P/N 60108-001) and temperature/humidity sensors 
(P/N 60108-002). They click into place in the sensor ports on the front of the unit.

Power Connection

The RIM-750 is powered through its mini USB port. Using the included cable, plug the 
mini end of the USB cable into the power jack on the RIM-750. Plug the enclosed USB 
wall charger into a standard wall outlet, and plug the UBS cable into it. The RIM-750 can 
also be powered by a USB connection on a server or another computer, just be sure 
the computer is plugged into a wall outlet, preferably one protected by a UPS.

Network Connection

Plug the network cable into an available network port and then into the network 
connection on the RIM-750.

Status LED

There are a variety of alarm and alert patterns and colors programmed for the RIM-
750’s LED. Use the following chart to determine which alarms are active.

Blink Pattern

Status Description

Solid Green

Normal status - no alarms are present

Lt. Blue/Blue

Alarm - Leak detection cable break

Lt. Blue/Off

Alarm - A leak has been detected

Red/Off

Alarm  - Temperature

Red/Blue

Alarm - Humidity

Magenta/Off

Alarm - Digital input

Yellow/Off

No network connection

Yellow/Magenta

Debug connection is active

Yellow/Lt. Blue

Configuration mode is active

White/Off

Unit is booting*

* Do not access or configure

the RIM-750 while these 

alerts are active.

Mixed

Firmware update is 

executing*

Red/Magenta

Call CPI - the RIM-750 has an internal error

Alarm Silence/Reset Button

If the audible alarm is active, push this button to silence it. Use the web interface or 
LED to determine the alarm condition. Advanced functions are also assigned to this 
button. Consult the troubleshooting guide on the RIM-750 web page 

https://www.

chatsworth.com/Remote-Infrastructure-Management-RIM-750

 for more information.

RIM-750: Rear Connections and Configuration Button

Digital Inputs

The RIM-750 can monitor eight digital inputs, each of which connects to the RIM-750 
through a 2-wire connection on the back of the unit. When you’re looking at the back of 
the unit, note that input 1 is on the right side of the terminal blocks, and input 8 is on 
the left side of the terminal blocks.

To connect your digital inputs to the RIM-750, loosen the screws on the appropriate 
slots on the terminal block connector, and insert the two wires from your digital input - 
one in each slot. Tighten the screws to secure the connections. 

Leak Detection Sensing Cable

Since leak detection sensing cable cannot connect directly to a controller, leader cable 
is used to connect leak detection cable to the RIM-750. 

1.  Remove the 4-pin terminal block connector from the back of the unit.
2.  Insert the four stripped wires of the leader cable into the appropriate slots in the 

terminal block connector - from left to right: white, black, green and red. Tighten 
the screws on the terminal block connector to secure the leader cable. Plug the 
connector, with the wires in the correct order, into the leak detection leader cable 
connection.

3.  Unscrew the EOL from the end of the leader cable.
4.  Attach the length of sensing cable to the leader cable.
5.  Route the sensing cable according to your cable layout diagram.
6.  Secure the EOL to the unoccupied end of the sensing cable. 

Relay Output

The RIM-750 has one relay output - use this to control an external 
device in the event of an alarm condition. Loosen the screws on the 
appropriate slots on the terminal block connector, and insert the wires for your relay 
output into the correct slots - NC-NO-C. Tighten the screws to secure the connections. 

Configuration Button

The configuration button is located on the back of the unit and is used for advanced 
troubleshooting. Consult the troubleshooting guide on the RIM-750 web page 

click here.

Mount the Controller

Once all connections have been wired to the RIM-750, mount the device in an 
appropriate location. CPI recommends a secure mounting through the keyhole cutouts 
on the enclosure or the optional 1U rack mount kit (P/N 60107-001).

Establish Communications

Through DHCP, the RIM-750 can be set up to communicate on your network. 
**Please NOTE: If DHCP is not available on your network, the RIM-750 will default to 
an IP address of 10.0.0.188. If this is the case at your facility, skip steps 1-3, enter the 
default IP address into your web browser address bar, and proceed to step 4.

1.  Plug the enclosed network cable into an available network port and then into the 

Network connection on the RIM-750. As soon as you plug the network cable into 
the powered RIM-750, DHCP assigns the RIM-750 an IP address. 

2.  Using a computer running on the same subnet as the RIM-750, open a web 

browser. In the web browser’s address bar, type cpi-serialnumber/ where serial 
number is the actual serial number of your RIM-750 (For example: cpi-a005ff/). Be 
sure to place the backslash after the serial number. This will ensure the browser 
executes a DNS lookup instead of a web search.

3.  Press enter. The browser will find the newly installed RIM-750 and allow you to 

access the RIM-750’s web interface.

4.  You may either leave the IP address as it is or change it to an IP address provided 

by your IT department. If you’d like to change the IP address, click the Setup tab, 
and then click on the Network link. Type the desired address into the IP address 
field, and click the Save Settings button.

Installation Supplies

Included with the RIM-750
RIM-750 device
Network cable
USB cable; USB mini B to USB A
5V USB wall charger

Available from CPI, sold separately
Temperature sensors (P/N 60108-001)
Temperature/humidity sensors (P/N 60108-002)
Leak Detection Lead Cable Kit (P/N 60116-001)

(1 required to attach conductive fluid sensing cables listed below) 

Conductive fluid sensing cable (P/N 60109-003, 10’L [3 m])
(P/N 60109-004, 25’L [7.6 m]) (P/N 60109-005, 50’L [15.2 m])
1U rack mount kit (P/N 60107-001)

Network Communications Information
The RIM-750’s serial number is found on a small, white sticker on the back of the unit, 
located under the connections for the digital inputs.

• 

RIM-750 Serial Number________________________________________

Consult your IT administrator to determine the following network settings 
for your RIM-750:

• 

IP Address _______________________________________________

• 

Subnet Mask _____________________________________________

• 

Default Gateway __________________________________________

** Wire all connections, sensors and power to the RIM-750 first. Then access the web 
interface to configure the device, and designate parameters and notification methods 
for your wired sensors, inputs and relays. 

RIM-750 Quick Start Guide

Thank you for purchasing the Remote Infrastructure Management (RIM-750) System 
from Chatsworth Products (CPI). This guide describes how to install and configure   
your unit.

If you need further assistance, please access the RIM-750 web page on our website 

https://www.chatsworth.com/Remote-Infrastructure-Management-RIM-750

, email our 

support staff directly at [email protected] or call us at
+1-800-834-4969.

Network 

Connection

Power 

Connection

1-Wire Sensor

Connections

Status

LED

Silence/Reset 

Button

Leak Detection

Leader Cable

Connection

Relay 

Output

Digital Input 

Connections

Configuration 

Button

RIM-750: Front Connections, Silence/Reset Button, and LED

While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for any errors or omissions and reserves the right to 

change information and descriptions of listed services and products. 

©2014 Chatsworth Products, Inc. All rights reserved. Chatsworth Products, CPI, CPI Passive Cooling, eConnect, MegaFrame, Saf-T-Grip, Seismic Frame, 

SlimFrame, TeraFrame, GlobalFrame, Cube-iT Plus, Evolution, OnTrac, QuadraRack and Velocity are federally registered trademarks of Chatsworth Products. 

Simply Efficient is a trademark of Chatsworth Products. All other trademarks belong to their respective companies. v2 08/20 MKT-60020-619