– PDU - Clone
Data from the Primary PDU can be cloned to the other PDUs in the Secure Array by
checking the desired parameters and selecting the PDUs to be cloned.
You can designate one of the linked PDUs as an Alternate PDU. The Alternate PDU
serves as a backup to the Primary PDU. It has a second and separate network connection
from the Primary PDU and assumes the Primary role, providing a network connection to
the PDUs in the array, if the Primary PDU loses connection. The Alternate PDU must be
equivalent to the Primary in functionality and outlet quantity in order to fully support
the array. Additionally, if deploying an Electronic Lock Kit, the Alternate PDU must have
the same user access information (ID card) from the primary PDU for the access logging
information to show up in the GUI.
Check the Alternate Primary check box, fill in the desired choices and click on
Save
.