CPI User Manual for eConnect PDU and Electronic Lock Kit 02/20.v2 4
Primary Role
: The role that is assigned to the PDU that is attached to the
network and serves as the beginning of the Secure Array. This PDU
should
have a level of functionality that is equal to or higher than that of all the
remaining PDUs within the array. In an array with several PDUs with the
highest level of functionality, the PDU with the most outlets among this
group should be assigned the Primary Role.
Secondary Role
: The role assigned to a PDU that is 1) linked to the primary
PDU, or 2) a standalone PDU.
Alternate Role:
The role assigned to the PDU that is connected to the
network to provide a backup network connection if the Primary Role PDU
loses power. This PDU must be equivalent to the Primary PDU in
functionality and number of outlets.
PRODUCT FEATURES
Vertically Mounted PDUs:
Physical Dimensions: refer to product cut sheet at
www.chatsworth.com
Input Voltage
:
100
– 415 Volts, varies by part number
Output Voltage
:
100
– 240 Volts, varies by part number
Input/Output Configurations
:
Please refer to the cut sheet for the
specific model available at chatsworth.com
Power Input Cable
:
Length: Standard: 10 ft (3 m)
Gauge: 6
– 12 AWG, varies by part number
Plug type: Current, Voltage and Configuration dependent,
varies by part number. Some PDUs have an IEC C20 Input
and do not include a power input cable.
Circuit Breakers
:
Type: Single or Double Pole Electro-hydraulic UL489 listed
Breakers Quantity: One, two, three or six, varies by part
number
Rating: 20 Amp
Receptacles
:
Types: NEMA, IEC, varies by part number
Quantity: Varies by part number
Rating: C13: 10 Amp, C19: 16 Amp; 5-20R: 16 Amp, varies
by part number
Single-phase unit. Actual
information displayed may vary
depending on whether the unit is
single- or three-phase.
Содержание eConnect EA Series
Страница 63: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 63...
Страница 65: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 65...
Страница 69: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 69...
Страница 71: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 71 HiD iClass Card...
Страница 72: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 72 MiFare Classic Card...
Страница 74: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 74 APPENDIX 2 Command Line Interface...