Holding Registers 

 

 

 

TYPE

ADDRESS DESCRIPTION

VALUE MEANING

ADDITIONAL NOTES

HOLD REG

40005

Total Cycle Time

0: 30 seconds
1: 60 seconds
2: 300 seconds (5 minutes)

HOLD REG

40006

Motor Size

Motor Size in RPM

HOLD REG

40009/40010

Timer On Time

On Time in Seconds (32 bit value)

9: lower word (16 bits)
10: upper word (16 bits)

HOLD REG

40011/40012

Timer Off Time

Off Time in Seconds (32 bit value)

11: lower word (16 bits)
12: upper word (16 bits)

HOLD REG

40013

Temperature Set point

Switched Set point or
Scaled Upper Temperature

deg F

HOLD REG

40014

Temperature Set point

Scaled Lower Temperature

deg F

HOLD REG

40015/40016

Minimum QPD 

QPD at Upper Temperature

float value
15: lower 16 bits
16: upper 16 bits

HOLD REG

40017/40018

Maximum QPD

QPD at Lower Temperature

float value
17: lower 16 bits
18: upper 16 bits

HOLD REG

40019/40020

QPD

Set Quarts/Day Value

float value
19: lower 16 bits
20: upper 16 bits

HOLD REG

40022/40023

Auxillary Timer On Time

On time in seconds (32 bit value)

22: lower word (16 bits)
23: upper word (16 bits)

HOLD REG

40024/40025

Auxillary Timer Off Time

Off time in seconds (32 bit value)

24: lower word (16 bits)
25: upper word (16 bits)

HOLD REG

40027/40028

Batch Delay / Batch Start

In seconds (32 bit value)
If Batch type = delay; this is the amount of delay (0-120 hours)
If Batch type=scheduled; this is the start time (0-23 hours)

27: lower word (16 bits)
28: upper word (16 bits)

HOLD REG

40029/40030

Batch Run Time

On time in seconds (32 bit value)

29: lower word (16 bits)
30: upper word (16 bits)

HOLD REG

40031/40032

Batch Amount

Auto mode batch volume in QPD

float value
31: lower 16 bits
32: upper 16 bits

HOLD REG

40033

Display Turn off

Time in seconds until display turns off

HOLD REG

40034

Cal Rate Pulses

Number of pulses counted in Cal Rate

0-999

HOLD REG

40035

Cal Rate Ticks

Number of ticks dropped in Cal Rate

Where ticks = 1Quart per Day per 1 Minute Test interval
(Standard rate gauge increment for Kenco 929 or similar)

HOLD REG

40036

Tank #1 Low Value

Low Scale, minimum value  (Value=Inches*10)

5-1150; inches value input by user x 10

HOLD REG

40037

Tank #1 High Value

High Scale, maximum value (Value=Inches*10)

5-1150; inches value input by user x 10

HOLD REG

40038

Tank #2 Low Value

Low Scale, minimum value  (Value=Inches*10)

5-1150; inches value input by user x 10

HOLD REG

40039

Tank #2 High Value

High Scale, maximum value (Value=Inches*10)

5-1150; inches value input by user x 10

HOLD REG

40040

Tank #1 Low Calibration

12-bit ADC offset value

0-4095; Raw analog reading

HOLD REG

40041

Tank #1 High Calibration

12-bit ADC offset value

0-4095; Raw analog reading

HOLD REG

40042

Tank #2 Low Calibration

12-bit ADC offset value

0-4095; Raw analog reading

HOLD REG

40043

Tank #2 High Calibration

12-bit ADC offset value

0-4095; Raw analog reading

HOLD REG

40044

Tank #1 Low Alarm

Alarm Trip point, Tank 1 
(Value=Inches*10)

0.5-115.0

HOLD REG

40045

Analog #1 Select

0: disabled
1: Inches
2: Raw

HOLD REG

40046

Tank #2 Low Alarm

Alarm Trip point, Tank 2
(Value=Inches*10)

0.5-115.0

HOLD REG

40047

Analog #2 Select

0: disabled
1: Inches
2: Raw

HOLD REG

40048

Cal method set

0: measured
1: calibrated
2: calculated

Lower byte used only
Calibration method selected by user

10MAY21

CODE VERSION

CHANGE NOTES

Содержание DigiUltra

Страница 1: ...ation 2 Adjusting Serial Port Settings 3 Serial Connections 4 Connecting to Serial Radios 4 Critical Radio Network Settings 4 Converting to RS232 Communication 4 Modbus TCP IP Connections 5 Tiny Gateway Connections 5 Critical Device Settings 5 Overview This document will assist with configuring the serial communications on the DigiUltra pump controller Comm Specifications Protocol Modbus RTU Conne...

Страница 2: ...reen 4 When CONTROLLER SETTINGS is shown press YES to enter sub menu 5 The screen below will be shown when entering the controller settings sub menu press MENU to scroll through options until COMMUNICATION is shown 6 When COMMUNICATION is shown use the YES NO buttons to scroll through options until ENABLED is shown 7 When ENABLED is shown press MENU to lock in setting and advance through the contr...

Страница 3: ...nu NOTE Communication is enabled by default but if COMMUNICATION SETTINGS is not available as a programming menu option see section on ENABLING COMMUNICATION 5 Use the buttons to adjust the MODBUS ADDRESS to the desired address Press MENU to advance when the desired address is shown default address is 16 6 Use YES NO Keys to adjust the desired baud rate of the controller Allowable options are 4800...

Страница 4: ...s are set the same on all radios in the network Frequency Key Mininum Packet Size Maximum Packet Size Network ID RF Data Rate If using parallel repeaters Frequency Key setting may differ between devices Call book may be used in place of Network ID but the appropriate serial number must be listed in the Call Book for each radio Converting to RS232 Communication The DigiUltra controller comes with M...

Страница 5: ...Connections Adding a Tiny Gateway or other Serial to Ethernet device server allows the DigiUltra controller to communicate via Modbus TCP IP To connect a Tiny Gateway device such as a TGW 715 or TGW 718 see the wiring diagram below Critical Device Settings DHCP Enabled Disabled IP Address Default Gateway Subnet Mask Baud Rate Baud rate set on device server for serial communication must match the D...

Страница 6: ...485 disabled 1 RS 485 enabled COIL 11 Head Configuration 0 Single head 1 Dual head COIL 12 Batch Mode 0 manual intermittent 1 auto qpd COIL 14 Timing Mode 0 intermittent 1 real time COIL 15 Cycle Mode 0 manual 1 auto COIL 16 Real Time Mode 0 TOD on on time 1 TOD on TOD off COIL 17 Low Voltage Scaling 0 disabled 1 enabled COIL 18 Solar Output 0 disabled 1 enabled COIL 19 Override Input Enable 0 dis...

Страница 7: ...changed DISC INPUT 10007 RTC Low Battery 1 RTC battery is below 2 3 volts DISC INPUT 10008 Digital Input 1 Signal Detected 0 No Signal Status of Digital Input processor pin RB15 DISC INPUT 10014 Motor Output 0 Main Output Currently Off 1 Main Output Currently On DISC INPUT 10010 Auxillary Output 0 Aux Output Currently Off 1 Aux Output Currently On DISC INPUT 10011 Write EEPROM Flag to indicate if ...

Страница 8: ...wer word 18 upper word INPUT REG 30019 30020 Total Quarts Pumped Number of quarts pumped calculated calibrated mode Float 19 lower word 20 upper word INPUT REG 30021 30022 Day Total Quarts Number of quarts pumped for the current day Float 21 lower word 22 upper word INPUT REG 30023 30024 Week Total Quarts Number of quarts pumped for the current week Float 23 lower word 24 upper word INPUT REG 3002...

Страница 9: ...0 upper word 16 bits HOLD REG 40031 40032 Batch Amount Auto mode batch volume in QPD float value 31 lower 16 bits 32 upper 16 bits HOLD REG 40033 Display Turn off Time in seconds until display turns off HOLD REG 40034 Cal Rate Pulses Number of pulses counted in Cal Rate 0 999 HOLD REG 40035 Cal Rate Ticks Number of ticks dropped in Cal Rate Where ticks 1Quart per Day per 1 Minute Test interval Sta...

Страница 10: ...d only Value voltage set 10 no decimal displayed HOLD REG 40062 Plunger Size 1 0 3 16 Inch 1 1 4 Inch 2 3 8 Inch 3 1 2 Inch Lower byte used only HOLD REG 40063 Plunger Size 2 0 3 16 Inch 1 1 4 Inch 2 3 8 Inch 3 1 2 Inch Lower byte used only HOLD REG 40064 Pin Position 1 1 2 or 3 HOLD REG 40065 Pin Position 2 1 2 or 3 HOLD REG 40066 Temperature Mode Disabled 0 Switched 1 Scaled 2 Lower byte used on...

Отзывы: