background image

NORRISEAL-WELLMARK 

REVISION 2021-5-14 

Input Registers 

 

 

 

TYPE

ADDRESS DESCRIPTION

VALUE MEANING

ADDITIONAL NOTES

INPUT REG

30000/30001

Version number

Compile Date

Version Number: compile date (YYMMDD) as integer
Eg: August 30, 2019 would be 190830 or 0x0002e96e in hex
(Register 1 * 65536) + Register 0 = Version Number

INPUT REG

30002/30003

Cycles

Current Number of Cycles

2: lower word
3: upper word

INPUT REG

30004

Temperature

Current Temperature as read by ADC

-40 to 140 degrees Fahrenheit

INPUT REG

30005/30006

Voltage

Current Voltage

float value
5: lower 16 bits
6: upper 16 bits

INPUT REG

30007

Analog Input #1

Raw ADC value

0-4095

INPUT REG

30008

Analog Input #2

Raw ADC value

0-4095

INPUT REG

30009

Analog #1 Inch Value

Calculated Inch value based on ADC

5-1150 (multipled by 10)

INPUT REG

30010

Analog #2 Inch Value

Calculated Inch value based on ADC

5-1150 (multipled by 10)

INPUT REG

30011/30012

Measured QPD

Measured (via pulse input) value of Quarts/Day

float value
11: lower 16 bits
12: upper 16 bits

INPUT REG

30013/30014

Day Cycles

Number of cycles counted for the current day

13: lower word
14: upper word

INPUT REG

30015/30016

Week Cycles

Number of cycles counted for the current week

15: lower word
16: upper word

INPUT REG

30017/30018

Month Cycles

Number of cycles counted for the current month

17: lower word
18: upper word

INPUT REG

30019/30020

Total Quarts Pumped

Number of quarts pumped; calculated/calibrated mode

Float
19: lower word
20: upper word

INPUT REG

30021/30022

Day Total Quarts

Number of quarts pumped for the current day

Float
21: lower word
22: upper word

INPUT REG

30023/30024

Week Total Quarts

Number of quarts pumped for the current week

Float
23: lower word
24: upper word

INPUT REG

30025/30026

Month Total Quarts

Number of quarts pumped for the current month

Float
25: lower word
26: upper word

INPUT REG

30027

Cal Method Used

0: measured
1: calibrated
2: calculated

Attempts to use value stored in holding register 48
If set = calibrated and no calibration exists, defaults to 
calculated
If set = measured and calibration exists / no pulses were detected, 
defaults to calibrated

INPUT REG

30028

AutoOnCounts

Calculated On Time; Auto mode

INPUT REG

30029

AutoOffCounts

Calculated Off Time; Auto mode

INPUT REG

30030/30031

Quarts/Second head #1

from Calculated or Measured modes

Float
30: lower word
31: upper word

INPUT REG

30032/30033

Quarts/Second head #2

from Calculated or Measured modes

Float
32: lower word
33: upper word

INPUT REG

30034

cal_pulses

0 – 59

INPUT REG

30035

cal_ticks

0 – 59

INPUT REG

30036

Total Run Seconds

0 – 4,294,967,295

Seconds are NOT saved to EEPROM

INPUT REG

30037

Total Run Minutes

16 bit unsigned

INPUT REG

30038/30039

Total Run Hours

38: lower word
39: upper word

INPUT REG

30040

Pulses/Cycle

Pulses expected per cycle for measured mode

10MAY21

CODE VERSION

CHANGE NOTES

Содержание DigiUltra

Страница 1: ...ation 2 Adjusting Serial Port Settings 3 Serial Connections 4 Connecting to Serial Radios 4 Critical Radio Network Settings 4 Converting to RS232 Communication 4 Modbus TCP IP Connections 5 Tiny Gateway Connections 5 Critical Device Settings 5 Overview This document will assist with configuring the serial communications on the DigiUltra pump controller Comm Specifications Protocol Modbus RTU Conne...

Страница 2: ...reen 4 When CONTROLLER SETTINGS is shown press YES to enter sub menu 5 The screen below will be shown when entering the controller settings sub menu press MENU to scroll through options until COMMUNICATION is shown 6 When COMMUNICATION is shown use the YES NO buttons to scroll through options until ENABLED is shown 7 When ENABLED is shown press MENU to lock in setting and advance through the contr...

Страница 3: ...nu NOTE Communication is enabled by default but if COMMUNICATION SETTINGS is not available as a programming menu option see section on ENABLING COMMUNICATION 5 Use the buttons to adjust the MODBUS ADDRESS to the desired address Press MENU to advance when the desired address is shown default address is 16 6 Use YES NO Keys to adjust the desired baud rate of the controller Allowable options are 4800...

Страница 4: ...s are set the same on all radios in the network Frequency Key Mininum Packet Size Maximum Packet Size Network ID RF Data Rate If using parallel repeaters Frequency Key setting may differ between devices Call book may be used in place of Network ID but the appropriate serial number must be listed in the Call Book for each radio Converting to RS232 Communication The DigiUltra controller comes with M...

Страница 5: ...Connections Adding a Tiny Gateway or other Serial to Ethernet device server allows the DigiUltra controller to communicate via Modbus TCP IP To connect a Tiny Gateway device such as a TGW 715 or TGW 718 see the wiring diagram below Critical Device Settings DHCP Enabled Disabled IP Address Default Gateway Subnet Mask Baud Rate Baud rate set on device server for serial communication must match the D...

Страница 6: ...485 disabled 1 RS 485 enabled COIL 11 Head Configuration 0 Single head 1 Dual head COIL 12 Batch Mode 0 manual intermittent 1 auto qpd COIL 14 Timing Mode 0 intermittent 1 real time COIL 15 Cycle Mode 0 manual 1 auto COIL 16 Real Time Mode 0 TOD on on time 1 TOD on TOD off COIL 17 Low Voltage Scaling 0 disabled 1 enabled COIL 18 Solar Output 0 disabled 1 enabled COIL 19 Override Input Enable 0 dis...

Страница 7: ...changed DISC INPUT 10007 RTC Low Battery 1 RTC battery is below 2 3 volts DISC INPUT 10008 Digital Input 1 Signal Detected 0 No Signal Status of Digital Input processor pin RB15 DISC INPUT 10014 Motor Output 0 Main Output Currently Off 1 Main Output Currently On DISC INPUT 10010 Auxillary Output 0 Aux Output Currently Off 1 Aux Output Currently On DISC INPUT 10011 Write EEPROM Flag to indicate if ...

Страница 8: ...wer word 18 upper word INPUT REG 30019 30020 Total Quarts Pumped Number of quarts pumped calculated calibrated mode Float 19 lower word 20 upper word INPUT REG 30021 30022 Day Total Quarts Number of quarts pumped for the current day Float 21 lower word 22 upper word INPUT REG 30023 30024 Week Total Quarts Number of quarts pumped for the current week Float 23 lower word 24 upper word INPUT REG 3002...

Страница 9: ...0 upper word 16 bits HOLD REG 40031 40032 Batch Amount Auto mode batch volume in QPD float value 31 lower 16 bits 32 upper 16 bits HOLD REG 40033 Display Turn off Time in seconds until display turns off HOLD REG 40034 Cal Rate Pulses Number of pulses counted in Cal Rate 0 999 HOLD REG 40035 Cal Rate Ticks Number of ticks dropped in Cal Rate Where ticks 1Quart per Day per 1 Minute Test interval Sta...

Страница 10: ...d only Value voltage set 10 no decimal displayed HOLD REG 40062 Plunger Size 1 0 3 16 Inch 1 1 4 Inch 2 3 8 Inch 3 1 2 Inch Lower byte used only HOLD REG 40063 Plunger Size 2 0 3 16 Inch 1 1 4 Inch 2 3 8 Inch 3 1 2 Inch Lower byte used only HOLD REG 40064 Pin Position 1 1 2 or 3 HOLD REG 40065 Pin Position 2 1 2 or 3 HOLD REG 40066 Temperature Mode Disabled 0 Switched 1 Scaled 2 Lower byte used on...

Отзывы: