background image

 

SL595 Variable Speed 

Motor Learn Instruction

 

 

01-34753A

 

1

 

 

APPLICATION REQUIREMENTS: 

This instruction is intended for use with the SL595 Variable Speed operators as a supplemental instruction to the standard 
SL595 manual, 01-34850.  All other installation, programming, and configuration information should refer to the 01-34850 
manual. 
 

PROGRAMMING INSTRUCTIONS 

 

BEFORE STARTING 

 

Before starting, the operator should be correctly installed 
and connected to the gate.  The gate operator should 
not be run until after the motor is learned.  The limit nut 
should be adjusted so that the gate can travel several 
feet in either direction without hitting a limit. 
 

MOTOR LEARN FUNCTION (FORCE 
PROFILE) 

 

In order to accurately set the force control for the 
operator, the control board must “learn” the specific RPM 
profile for your operator.  This is done using the red 
button, “S3”, located at the end of the control board, next 
to the microprocessor. 
 

NOTE:

 Motor learn must be performed in stand alone 

mode while running at its slowest speed setting as set by 
the main speed potentiometer.  The gate must be 
correctly installed and connected to the operator. 

 

1.  Set the gate speed to the slowest setting by turning 

the main speed potentiometer (located in front of the 
small control board) fully counter-clockwise. 

2.  Press the motor learn button (S3) on the main control 

board.  The yellow LED should start to flash rapidly. 

 

 

 
3.  Push and hold down either the open or the close 

buttons.  The motor will run for a few seconds and 
then stop.  If the LED goes out the motor is learned.  

If the unit hits a limit before completing the learn 
sequence or some other error occurs, the LED will go 
back to “on” continuously.  If this happens, try 
learning the motor in the opposite direction. 

 

COMPLETING THE INSTALLATION 

 
The limits and other aspects of the operator can be 
configured at this time.  Refer to the main operator 
manual, 01-34850, for these instructions. 
 
After the limits are set and the gate is operating as 
intended, the main speed potentiometer can be adjusted 
as desired.  Verify that the gate can run the full open and 
close distances without incident after adjusting the main 
speed potentiometer. 
 

NOTE:

 If the gate cannot move at full speed without 

stopping, the motor profile must be re-learned at a 
higher minimum speed.  To do this, increase the 
minimum speed by turning the Min Speed Trimpot 
clockwise.  Adjust the Main Speed Potentiometer to its 
minimum setting (fully counter clockwise) and repeat the 
motor learn process.  
 

 

 

Min Speed 

Trimpot 

Main Speed 

Potentiometer 