Functional Description
151
If the speed of the pump reaches the lower band limit, the
'top' pump is stopped immediately without delay. If a stop
delay is used this delay will be ignored. Range is from 0%,
equalling min speed, to the set percentage for the “Lower
Band [398]”.
Communication information
Fig. 118 Lower band limit
The settle start allows the process to settle after a pump is
switched on before the pump control continues. If an
additional pump is started D.O.L. (Direct On Line) or Y/
,
the flow or pressure can still fluctuate due to the 'rough'
start/stop method. This could cause unnecessary starting
and stopping of additional pumps.
During the Settle start:
•
PID controller is off.
•
The speed is kept at a fixed level after adding a pump.
Communication information
The transition speed start is used to minimize a flow/
pressure overshoot when adding another pump. When an
additional pump needs to be switched on, the master pump
will slow down to the set transition speed start value, before
the additional pump is started. The setting depends on the
dynamics of both the master drive and the additional drives.
The transition speed is best set by trial and error.
In general:
•
If the additional pump has 'slow' start/stop dynamics,
then a higher transition speed should be used.
•
If the additional pump has 'fast' start/stop dynamics,
then a lower transition speed should be used.
Communication information
Example
Max Speed = 1500 rpm
Min Speed = 200 rpm
TransS Start = 60%
When an additional pump is needed, the speed will be
controlled down to min speed + (60% x (1500 rpm - 200
rpm)) = 200 rpm + 780 rpm = 980 rpm. When this speed is
reached, the additional pump with the lowest run time
hours will be switched on.
39C
Low Band Lim
Default:
0%
Range:
0 to Lower Band level. 0% (=min speed)
means that he Limit function is switched off.
Modbus Instance no/DeviceNet no:
43172
Profibus slot/index
169/76
EtherCAT and CANopen index (hex)
4c64
Profinet IO index
19556
Fieldbus format
Long, 1=1%
Modbus format
EInt
39D
Settle Start
Default:
0 s
Range:
0-999 s
(NG_50-PC-15_2)
Speed
Max
Min
Lower band
Stop Delay [39A]
Lower band
limit [39C]
“top” pump stops
immediately
Flow/Pressure
Δ
Modbus Instance no/DeviceNet no:
43173
Profibus slot/index
169/77
EtherCAT and CANopen index (hex)
4c65
Profinet IO index
19557
Fieldbus format
Long, 1=1 s
Modbus format
EInt
39E
TransS Start
Default:
60%
Range:
0-100% of total min speed to max speed
Modbus Instance no/DeviceNet no:
43174
Profibus slot/index
169/78
EtherCAT and CANopen index (hex)
4c66
Profinet IO index
19558
Fieldbus format
Long, 1=1%
Modbus format
EInt
NOTE: If set to 100 %, the transition speed, when
starting pumps, is ignored and no speed adaption is
made.
I.e. the slave pump is started directly and speed of
the master pump is maintained.
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......