Functional Description
CG Drives & Automation, 01-5326-01r5
Acceleration Time Motor
Potentiometer [333]
It is possible to control the speed of the AC drive using the
motor potentiometer function. This function controls the
speed with separate up and down commands, over remote
signals. The MotPot function has separate ramps settings
which can be set in “Acc MotPot [333]” and “Dec MotPot
[334]”.
If the MotPot function is selected, this is the acceleration
time for the MotPot up command. The acceleration time is
defined as the time it takes for the motor potentiometer
value to increase from 0 rpm to nominal speed.
Communication information
Deceleration Time Motor
Potentiometer [334]
If the MotPot function is selected, this is the deceleration
time for the “MotPot” down command. The deceleration
time is defined as the time it takes for the motor
potentiometer value to decrease from nominal speed to 0
rpm.
Communication information
Acceleration Time to Minimum
Speed [335]
If minimum speed, [341]>0 rpm, is used in an application,
the AC drive uses separate ramp times below this level. With
“Acc<MinSpeed [335]” and “Dec<MinSpeed [336]” you can
set the required ramp times. Short times can be used to
prevent damage and excessive pump wear due too little
lubrication at lower speeds. Longer times can be used to fill
up a system smoothly and prevent water hammer due to
rapidly exhausting air from the pipe system.
If a Minimum speed is programmed, this parameter will be
used to set the the acceleration time parameter [335] for
speeds up to minimum speed at a run command. The ramp
time is defined as the time it takes for the motor to
accelerate from 0 rpm to nominal motor speed.
Communication information
Fig. 100 Calculation example of accelerating times
(graphics not proportional).
333
Acc MotPot
Default:
16.0 s
Range:
0.50–3600 s
Modbus Instance no/DeviceNet no:
43103
Profibus slot/index
169/7
EtherCAT and CANopen index (hex)
4c1f
Profinet IO index
19487
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
334
Dec MotPot
Default:
16.0 s
Range:
0.50–3600 s
Modbus Instance no/DeviceNet no:
43104
Profibus slot/index
169/8
EtherCAT and CANopen index (hex)
4c20
Profinet IO index
19488
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
335
Acc<Min Spd
Default:
10.0 s
Range:
0-3600 s
Modbus Instance no/DeviceNet no:
43105
Profibus slot/index
169/9
EtherCAT and CANopen index (hex)
4c21
Profinet IO index
19489
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
time
rpm
Motor Speed
Max speed
Min speed
[341]
[343]
[225]
3000
600
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......