CG Drives & Automation,01-5326-01r5
Functional Description
99
Set the nominal asynchronous motor speed.
Communication information
When the nominal speed of the motor is
≤
500 rpm, the
additional menu for entering the number of poles, [226],
appears automatically. In this menu the actual pole number
can be set which will increase the control accuracy of the AC
drive.
Communication information
Motor Cos
ϕ
Set the nominal Motor cosphi (power factor).
Communication information
Parameter for setting the type of motor ventilation. Affects
the characteristics of the I
2
t motor protection by lowering
the actual overload current at lower speeds.
Communication information
When the motor has no cooling fan, None is selected and
the current level is limited to 55% of rated motor current.
With a motor with a shaft mounted fan, Self is selected and
the current for overload is limited to 87% from 20% of
synchronous speed. At lower speed, the overload current
allowed will be smaller.
When the motor has an external cooling fan, Forced is
selected and the overload current allowed starts at 90% from
rated motor current at zero speed, up to nominal motor
current at 70% of synchronous speed.
Fig. 94 shows the characteristics with respect for Nominal
Current and Speed in relation to the motor ventilation type
selected.
225 Motor
Speed
Default:
(n
MOT
)
rpm (see Note 2 page 97)
Range:
30 - 18000 rpm
Resolution
1 rpm, 4 sign digits
WARNING!
Do NOT enter a synchronous (no-load)
motor speed.
NOTE: Maximum speed [343] is not automatically
changed when the motor speed is changed.
NOTE: Entering a wrong, too low value can cause a
dangerous situation for the driven application due to
high speeds.
Modbus Instance no/DeviceNet no:
43045
Profibus slot/index
168/204
EtherCAT and CANopen index (hex)
4be5
Profinet IO index
19429
Fieldbus format
UInt. 1=1 rpm
Modbus format
UInt
226
Motor Poles
Default:
4
Range:
2-144
Modbus Instance no/DeviceNet no:
43046
Profibus slot/index
168/205
EtherCAT and CANopen index (hex)
4be6
Profinet IO index
19430
Fieldbus format
Long, 1=1 pole
Modbus format
EInt
227 Motor
Cos
ϕ
Default:
Cos
ϕ
NOM
(see Note 2 page 97)
Range:
0.45 - 1.00
Modbus Instance no/DeviceNet no:
43047
Profibus slot/index
168/206
EtherCAT and CANopen index (hex)
4be7
Profinet IO index
19431
Fieldbus format
Long, 1=0.01
Modbus format
EInt
228 Motor
Vent
Default:
Self
None
0 Limited I
2
t overload curve.
Self
1
Normal I
2
t overload curve. Means that the
motor stands lower current at low speed.
Forced
2
Expanded I
2
t overload curve. Means that
the motor stands almost the whole current
also at lower speed.
Modbus Instance no/DeviceNet no:
43048
Profibus slot/index
168/207
EtherCAT and CANopen index (hex)
4be8
Profinet IO index
19432
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......