96
Functional Description
CG Drives & Automation, 01-5326-01r5
11.4.2 Remote Signal Level/Edge
In this menu you select the way to control the inputs for
RunR, RunL and Reset that are operated via the digital
inputs on the terminal strip. The inputs are default set for
level-control, and will be active as long as the input is made
and kept high. When edge-control is selected, the input will
be activated by the low to high transition of the input. See
Chapter 7.2 page 64 for more information.
Communication information
11.4.3 Mains supply voltage [21B]
In this menu the nominal mains supply voltage connected to
the AC drive can be selected. The setting will be valid for all
parameter sets. The default setting, Not defined, is never
selectable and is only visible until a new value is selected.
This menu specifies the AC supply voltage. The
corresponding DC voltage is 1.34 times higher.
Once the supply voltage is set, this selection will not be
affected by the Load Default command [243].
Brake chopper activation level is adjusted using the setting
of [21B].
Communication information
21A
Level/Edge
Default:
Level
Level
0
The inputs are activated or deactivated
by a continuous high or low signal. Is
commonly used if, for example, a PLC is
used to operate the AC drive.
Edge
1
The inputs are activated by a transition;
for Run and Reset from “low” to “high”
and for Stop from "high" to "low".
Modbus Instance no/DeviceNet no:
43020
Profibus slot/index
168/179
EtherCAT and CANopen index (hex)
4bcc
Profinet IO index
19404
Fieldbus format
UInt
Modbus format
UInt
CAUTION!
Level controlled inputs DO NOT comply with
the Machine Directive if the inputs are
directly used to start and stop the machine.
NOTE: Edge controlled inputs can comply with the
Machine Directive (see the Chapter 8. page 69) if the
inputs are directly used to start and stop the
machine.
!
WARNING!
This menu must be set according to the
AC drive product label and the supply
voltage used. Wrong setting might damage
the AC drive or brake resistor.
NOTE: The setting is affected by the “Load from CP”
command [245] and if loading parameter file via
EmoSoftCom.
21B
Supply Volts
Default:
Not defined
Not Defined
0
Inverter default value used. Only valid if
this parameter is never set.
220-240 VAC 1
Only valid for VFX48/52
380-415 VAC 3
Only valid for VFX48/52/69
440-480 VAC 4
Only valid for VFX48/52/69
500-525 VAC 5
Only valid for VFX52/69
550-600 VAC 6
Only valid for VFX69
660-690 VAC 7
Only valid for VFX69
Modbus Instance no/DeviceNet no:
43381
Profibus slot/index
170/30
EtherCAT and CANopen index (hex)
4d35
Profinet IO index
19765
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......