Functionality
CG Drives & Automation, 01-5980-01r2
Action Control [215]
These menus are used to select the source for run and stop
commands and for jog control. This is described in section
7.1, page 49.
Run/Stop Control [2151]
This menu is used to select the control source for run and
stop commands.
Jog Control [2152]
In this menu the control source for the jog function is
selected. If the Jog FWD and Jog REV keys are to be used,
one of the keyboard alternatives must be selected in this
menu, and the keyboard must be locked in menu [218].
See section 7.1.3, page 50 for settings regarding the jog
functions.
Reset Control [216]
When the softstarter is in alarm condition, a reset
command is required to make it possible to restart the
softstarter. Use this function to select the source of the reset
signal. The keyboard alternatives in this menu enable both
external and internal control panels to be used. For autoreset
settings, see menu group [250] “Autoreset”. See also section
7.3.5, page 60 about reset and autoreset functions.
Default:
Remote
Remote
0
Start/stop command via digital input or
Virtual I/O.
Int+Ext
keyb
1
Start/stop command via internal or external
control panel.
Com
2
Start/stop command via serial
communication.
Int keyb
5
Start/stop command via internal control
panel.
Ext keyb
6
Start/stop command via external control
panel.
Default:
Remote
Remote
0
Jog command via digital input or Virtual I/O.
Int+Ext
keyb
1
Jog command via internal or external
control panel.
Com
2
Jog command via serial communication.
Int keyb
5
Jog command via internal control panel.
Ext keyb
6
Jog command via external control panel.
2151 Run/Stp Ctrl
Stp
Remote
2152 Jog Ctrl
Stp
Remote
WARNING!
If the input signal Run FWD/RunREV is active
(high) and level-controlled start mode is
selected, the motor will start at the reset
command.
Note that “level control” is not fulfilling the
Machine directive
Default:
Keyb
Remote
0
Reset command via digital input or
Virtual I/O.
Keyboard
1
Reset command via internal or external
control panel (RESET key).
Com
2
Reset command via serial
communication.
keyb
3
Reset command via digital input or
control panel (internal or external).
Com+keyb 4
Reset command via serial
communication or control panel (internal
or external).
Rem+keyb
+com
5
Reset command via digital input, control
panel (internal or external), or serial
communication.
216 Reset Ctrl
Stp
Keyb
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......