![CG emotron TSA Series Скачать руководство пользователя страница 139](http://html1.mh-extra.com/html/cg/emotron-tsa-series/emotron-tsa-series_instruction-manual_2585387139.webp)
CG Drives & Automation, 01-5980-01r2
Functionality
135
8.8
View Trip Log [800]
Main menu with parameters for viewing all the logged trip
data. In total the softstarter saves the last 9 trips in the trip
memory. The trip memory refreshes on the FIFO principle
(First In, First Out). Every trip in the memory is logged on
actual date and the time. At every trip, the actual values of
several parameters are stored and available for
troubleshooting.
See section 7.3.1, page 55 for an explanation of the different
alarm types.
8.8.1
Trip Message Log [810]
The trip log displays the cause of the trip and what time it
occurred (based on the actual time in [740]). The display is
showing actual trip message and alternates between showing
date and time when the trip occured.
See a list of the possible trip messages in Table 36, page 132.
When a trip occurs the operation and status menus [710] and
[720]are copied to the trip message log. There are nine trip
message logs [810]–[890]. When the tenth trip occurs the
oldest trip message will be erased.
Example:
The display is showing actual trip message and alternates
between showing date and time when the trip occurred
For fieldbus integer value of trip message, see Table 36, page
132 (menu [722]).
Trip message [8111]-[8133]
The information from the status menus are copied to the trip
message log when a trip occurs.
NOTE: After the reset of a trip, the previous menu will
appear.
Unit:
Alternating
hh:mm:ss (hours: minutes: seconds)
YYYY-MM-DD (year-month-day)
8x0 Trip Message
Trp hh:mm:ss
830 Locked Rotor
Trp 09:12:14
830 Locked Rotor
Trp 2013-04-17
Table 37
Stored trip message parameters
Trip menu Copied from
Description
8111
711
Process Value
8113
713
Torque (Nm)
8114
714
Torque (%)
8115
715
Shaft Power (W)
8116
716
Shaft Power (%)
8117
717
El Power
8118
718
RMS Current
8119
719
L Main Volt
811A
71A
Heatsink Temp
811B
71B
PT100B1 123
811C
71C
PT100B2 123
811D
71D
Current I1
811E
71E
Current I2
811F
71F
Current I3
811G
71G
L12 Voltage
811H
71H
L13 Voltage
811I
71I
L23 Voltage
811J
71J
Phase Seq
811K
71K
Used Thermal Cap
8121
721
TSA Status
8122
723
Digital input status
8123
724
Relay status
8124
725
Analogue input status
8125
726
Analogue output status
8126
727
I/O status option board B1
8127
728
I/O status option board B2
8129
72A
Analogue comparator 1 - 4
812A
72B
Digital comparator 1 - 4
812B
72C
Logic function status 1-4
812C
72D
Timer status 1-4
812D
72E
Flip-flop status 1-4
812E
72F
Counter status 1-2
812F
72G
Time to next start
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......