Installation
Important notes
5
CG Drives & Automation
41
5
Installation
5.1
Important notes
Danger!
Hazardous electrical voltage
Terminals T1, T2 are on
DC−bu
s voltage potential.
Possible consequences:
Death or severe injuries when touching the power terminals.
Protective measures:
Before working on the terminals, disconnect mains and wait for at least
3 minutes.
Check whether the terminals are deenergised.
Danger!
Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
Death or severe injuries when touching the device in the event of an error.
Protective measures:
Implement the measures required in EN
61800−5−1.
Especially:
Fixed installation
–
Implement PE connection in compliance with standards.
–
Connect PE conductor twice or PE conductor
cross−sectio
n
>
10 mm
2
.
Connection with a connector for industrial applications according to
IEC 60309 (CEE):
–
PE conductor
cross−sectio
n
>
2.5 mm
2
as part of a
multi−cor
e supply cable.
–
Provide for suitable strain relief.
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
Death or severe injuries when touching the power terminals.
Protective measures:
Switch off the power supply and wait for at least three minutes before
working on the power terminals.
Make sure that all power terminals are deenergised.