Installation
44
CG Drives & Automation
Safety instructions for the installation according to UL/CSA
5.2
Safety instructions for the installation according to UL/CSA
Original −
English
Warnings!
These devices are suitable for field wiring.
Intended for use with 75 °C wire.
Intended for use with copper conductors only.
Suitable for use in a surrounding air temperature of 45 °C, and
– additionally 60 °C when
de−rating
rules are followed.
Hot surface. Risk of burn.
Should this device be mounted on a motor, the combination needs to be
suitable for the type rating.
The supply terminals are to be tightened to:
– For model suffix’s 0.75 – 2.2 kW tighten to 4.4
−
5.3
lb−in.
–
For model suffix’s 3.0 – 4 kW, tighten to 7
lb−in.
These devices are suitable for use on a circuit capable of delivering not more
than 200 000 rms Symmetrical Amperes, 480 V maximum
–
When protected by CC, R, T, or J class fuses or
–
When protected by a circuit breaker having an interrupting rating not less
than 200 000 rms symmetrical amperes, 480 V maximum.
Use fuses and circuit breakers only.
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with
the National Electrical Code and any additional local codes.
The opening of branch circuit protective devices may be an indication that a
fault current has been interrupted. To reduce the risk of fire or electric shock,
current carrying parts and other components, the controller should be
examined and replaced if damaged.
These devices provide overload protection rated for 125 % of the rated FLA.
CAUTION!
Risk of electric shock. Please allow 180 s for the internal capacitors to
discharge.