Technical data
s
22
CG Drives & Automation
Operation with normal duty on a 480 V system
4.2.2
Operation with normal duty on a 480 V system
The overload capacity is limited to 110 %/1 min. Typical applications are pumps with a
quadratic load characteristic, or fans.
Mains
Voltage
U
Lrated
[V]
Voltage range
U
Lrated
[V]
Frequency range
f [Hz]
3/PE AC
480
432
−
0 % ... 528 + 0 %
45 − 0 % ... 65 + 0
%
Type
Mains current
at I
arated
I
Lrated
[A]
Output power
U, V, W
S
arated
[kVA]
Motor power
4 pol. ASM
P
arated
[kW]
CDN40-2P2-65
1.8
1.3
0.75
CDN40-3P8-65
3.2
2.4
1.5
CDN40-4P8-65
3.8
3.0
2.2
CDN40-7P0-65
5.6
4.1
3.0
CDN40-8P7-65
7.2
5.3
4.0
CDN40-012-65
9.3
6.8
5.5
CDN40-016-65
12.8
9.4
7.5
Note!
Operation with normal duty overload is only permitted ...
with the rated data specified for the controller.
within the mains voltage range specified.
with the switching frequency 4 kHz.
at a max. ambient temperature of 40 °C
with the fuses and cable
cross−section
s specified for this operation.
after parameterisation according to the specifications (01-xxxx-yy
software manual)
Содержание CDN40-012-65
Страница 1: ...Emotron CDN Motor mounted AC drive 0 75 7 5 kW Hardware manual...
Страница 2: ......
Страница 70: ......
Страница 71: ......